7.0
Site Requirements – page 15
Fig. 11
Fig. 12
7.9
Flue Dimensions
See Section 1.2. The standard horizontal flue kit allows
for flue lengths between 200mm (7 7/8 in) and 1m
(39 3/8 in) from elbow to terminal (Fig. 11).
The maximum permissible equivalent flue length is:
4 metres.
NOTE: Each additional 45º of flue bend will account
for an equivalent flue length of 0.5m.
eg. 45º = 0.5m,
90º = 2 x 45º = 1m etc.
7.10
Flue Terminal Trim
1.
The trim should be fitted once the flue is secure.
2.
Take the three edge clips from the kit and fit equi-
spaced onto the inner flange of the trim (Fig. 11b).
3.
With the flanges towards the wall pass the trim over
the terminal (Fig. 11c). If required a bead of sealant
may be applied to the rear face of the trim.
4.
Push firmly on the trim to ensure the edge clips
engage on the flue.
7.11
Terminal Guard (Fig. 12)
1.
When codes of practice dictate the use of terminal
guards, they can be obtained from most Plumbers'
and Builders' Merchants.
2.
When ordering a terminal guard, quote the
appliance model number.
3.
The guard manufacturers listed below can be
contacted for terminal sizes and guard model
numbers.
Tower Flue Components Ltd.,
Tower House,
Vale Rise,
Tonbridge,
Kent.
Tel: 01732 351555.
Quinnell, Barrett & Quinnell,
884 Old Kent Road,
London,
SE15 1NL.
Tel: 0171 6391357.
4.
The flue terminal guard should be positioned
centrally over the terminal and fixed as illustrated.