Electric Characteristics - York YKCA-YKHA 18 Service Manual

4 way cassette
Table of Contents

Advertisement

8. Electric Characteristics

Indoors power supply wiring
Model
Hz
YKCA 18
(compact)
YKHA 18 (compact)
YKCA 18
YKHA 18
YKCA 24
YKHA 24
50
YKCA 36
YKHA 36
YKCA 36
YKHA 36
YKCA 48
YKHA 48
Symbols:
MCA: Min. Circuit Amps.
MFA: Max. Fuse Amps..
FLA: Full Load Amps.
Kw: Rate Motor Output
Notes:
5. Voltage range should not over the value of above table.
6. Maximum allowable voltage variation between phase is 2%
7. Selection wire size based on the larger value of MCA.
8. MCA/MFA
MCA = 1.25 × FLA
MFA ≤ 4 × FLA
(Next lower standard fuse rating min. 15A)
5. Instead of fuse, circuit breaker is also acceptable.
Indoor Units
Voltage
Min.
Max.
220-240
198
264
380
342
418
Power Supply
Indoor fan motor
MCA
MFA
kW
10.6
30
0.06
10.6
30
0.06
12.4
30
0.10
12.4
30
0.10
18.7
60
0.12
18.7
60
0.12
26
80
0.14
26
80
0.14
9.8
20
0.14
9.8
20
0.14
11.5
30
0.14
11.5
30
0.14
Power input(W)
FLA
Cooling
Heating
0.29
2050
0.29
2050
0.35
2050
0.35
2050
0.54
3000
0.54
3000
0.62
4400
0.62
4400
0.62
4400
0.62
4400
0.62
5400
0.62
5400
2100
2100
2950
4500
4500
5500

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ykca-ykha 36Ykca-ykha 48Ykca-ykha 24

Table of Contents