Vibration; Routine Maintenance And Operation; Fan Operation; Motors - Greenheck USF-200 Installation, Operation & Maintenance Manual

Utility and centrifugal fans
Table of Contents

Advertisement

Vibration

On start-up and during operation, the unit should
operate smoothly with minimal vibration. It is possible
that a higher degree of vibration may be experienced.
Excessive vibration if left unchecked, can cause a
multitude of problems, including structural and/or
Common Sources of Vibration
1. Wheel Unbalance
2. Drive Pulley Misalignment
3. Incorrect Belt Tension
4. Bearing Misalignment
5. Mechanical Looseness
6. Faulty Belts
7. Drive Component Unbalance
8. Poor Inlet/Outlet Conditions
9. Foundation Stiffness
manual for corrective actions. If observation cannot
locate the source of vibration, a qualified technician
using vibration analysis equipment should be
consulted. If the problem is wheel unbalance, in-place
balancing can be done through the access panel
located on the side of each fan's tubular housing.
Any correction weights added to the wheel should be
welded to either the wheel back (single-plane balance)
or to the wheel back and wheel cone (two-plane
balance).
12
Utility and Centrifugal Fans
Routine Maintenance and
Operation
When performing any service to the fan, disconnect
the electrical supply and secure fan impeller.
component failure.
The most common
Once the unit has been put into operation, a
sources of vibration
routine maintenance schedule should be set up to
are listed.
accomplish the following:
Many of these
1. Lubrication of bearings and motor.
conditions can
2. Wheel, housing, bolts and set screws on the entire
be discovered by
careful observation.
3. Any dirt accumulation on the wheel or in the
Refer to the
troubleshooting
section of this
4. Inspect fan impeller and housing looking for fatigue,

Fan Operation

All fans should be run every thirty (30) days, or at least
"bumped" every thirty days. It is preferred that each
fan is run as this causes all electrical and mechanical
components to get up to temperature, displacing any
formed condensation, redistributes load on bearings,
and redistributes grease in the bearings (motor and
shaft bearings).
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.),
consult manufacturer to determine if the unit can
operate safely at the new condition.

Motors

Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup
on the motor housing assists proper motor cooling.
Never wash-down motor with high pressure spray.
Greasing of motors is only intended when fittings are
provided. Many fractional motors are permanently
lubricated for life and require no further lubrication.
Motors supplied with grease fittings should be
greased in accordance with the manufacturer's
recommendations. When motor temperature does not
exceed 104ºF (40ºC), the grease should be replaced
after 2000 hours of running time.
Direct drive systems have extended grease lines to
lubricate the motor without removal of any guarding.
CAUTION
fan should be checked for tightness.
housing should be removed to prevent unbalance
and possible damage.
corrosion, or wear.
CAUTION
®

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Usf-300CswUsf-400

Table of Contents