Adjusting The Heating Curves (Only For Weather-Compensated Control Units) - Viessmann VITODENS 200-W Service Instructions Manual

Wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Further details regarding the individual steps
Adjusting the heating curves (only for weather-compensated
control units)
The heating curves illustrate the rela-
tionship between the outside tem-
perature and the boiler water or flow
temperature.
To put it simply: The lower the outside
temperature, the higher the boiler
water or flow temperature.
A Heating curve slope for underfloor
heating systems
Commissioning, inspection, maintenance
(cont.)
The room temperature, again,
depends on the boiler water or the
flow temperature.
Settings in the delivered condition:
Slope = 1.4
Level = 0
B Heating curve slope for low tem-
perature heating systems
(according to the Energy Savings
Order [Germany])
29