Setting The Maximum Output; Checking The Balanced Flue System For Tightness (Annular Gap Check) - Viessmann VITODENS 200-W Service Instructions Manual

Wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps

Setting the maximum output

Note
You can limit the maximum output for heating operation. The limit is set via the
modulation range. The max. adjustable heating output is limited upwards by the
boiler coding card.
1. Start the boiler.
2. Press K and F simultaneously
until a value flashes (e.g. "85") and
"A" appears. In the delivered con-
dition, this value represents 100 %
of rated output.
On weather-compensated control
units, the display additionally
shows "Max. output".
3. With a/b select the required
value in % of rated output as maxi-
mum output.
Checking the balanced flue system for tightness (annular
gap check)
A Combustion air port
16
(cont.)
4. Confirm the set value with d.
5. Record the settings for maximum
output on the additional type plate
included with the "technical docu-
mentation". Affix the type plate next
to the original type plate on top of
the boiler.
Note
The output can also be limited for
DHW heating. For this, change coding
address "6F" in code 2.