Liebert PDUTM Maintenance Manual page 94

Liebert corporation operation & maintenance power supply sts2, pdutm
Table of Contents

Advertisement

Table 12
Event messages (continued)
ID
Alarm Message
81
SOURCES OUT OF SYNC
82
LOAD ON ALT SOURCE
83
AUTO REXFER INHIBIT
84
CB1 (S1) OPEN
85
CB2 (S2) OPEN
86
CB4 (S1 BYP) CLOSED
87
CB5 (S2 BYP) CLOSED
88
CB3 (OUTPUT) OPEN
89
CB3A (OUTPUT) OPEN
90
S1 PHASE ROT ERROR
91
S2 PHASE ROT ERROR
92
TRANSFER INHIBITED
93
OUTPUT UV
94
HISTORY LOG FULL
96
INPUT 1 OV INPUT
97
INPUT 1 UV INPUT
98
INPUT 2 OV INPUT
99
INPUT 2 UV INPUT
100
LOAD OVERCURRENT
101
GROUND OVERCURRENT
102
NEUTRAL OVERCURRENT
103
LOAD VOLTAGE THD
104
INPUT 1 CB6 OPEN
105
INPUT 2 CB7 OPEN
106
INPUT 1 OF/UF
107
INPUT 2 OF/UF
120
INPUT CONTACT #1
121
INPUT CONTACT #2
122
INPUT CONTACT #3
123
INPUT CONTACT #4
124
INPUT CONTACT #5
125
INPUT CONTACT #6
126
INPUT CONTACT #7
127
INPUT CONTACT #8
128
CONFIG MODIFIED
129
PASSWORD CHANGED
130
TIME REPROGRAMMED
131
DATE REPROGRAMMED
132
EVENT LOG CLEARED
133
HIST LOGS CLEARED
134
XFER COUNT CLEARED
135
KWH COUNT CLEARED
Description/Cause
Source 1 and Source 2 are out of synchronization.
The output load is running on the alternate source.
Automatic retransfer is inhibited.
Source 1, Circuit Breaker 1 is open.
Source 2, Circuit Breaker 2 is open.
Source 1 on bypass, Circuit Breaker 4 is closed.
Source 2 on bypass, Circuit Breaker 5 is closed.
Output circuit breaker (CB3) is open.
Output circuit breaker (CB3A) is open.
Source 1 phase rotation error.
Source 2 phase rotation error.
Transfer inhibited.
Output is under voltage.
Both History Logs have been written and no more history logs can be
written without clearing one of the logs
Source 1 over voltage
Source 1 under voltage
Source 2 over voltage
Source 2 under voltage
Output over current
Ground over current
Neutral over curremt
Voltage THD has exceeded the set limit
Source 1 input Circuit Breaker 6 is open
Source 2 Input Circuit Breaker 7 is open
Source 1 over frequency/under frequency
Source 2 over frequency/under frequency
Input Contact # x is an optional alarm input. The alarm name can be
programmed with an alarm name from the Input Contactor Isolator
settings option under the Comm Options. See Configuring the Input
Contact Isolator Settings on page 108. The alarm is sent to Monitor
DSP. The LCD logs the alarm with the programmed name. Monitor
DSP logs it with the generic name which is how it is reported to the
SVT query.
A setpoint configuration has changed.
The password for touch screen access has been modified and saved.
The system's time has been reset and saved.
The system's date has been reset and saved.
The event log has been erased.
Both History Logs have been erased.
Transfer counter reset to 0
KW-Hrs counter reset to 0
86
Alarms and Faults
Action
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
D, F, A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
E
E
E
E
E
E
E
E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sts2

Table of Contents