Output Power Wiring; Customer Connections; Table 7 Distribution Configurations - Liebert PDUTM Maintenance Manual

Liebert corporation operation & maintenance power supply sts2, pdutm
Table of Contents

Advertisement

5.0
O
P
UTPUT
OWER
The STS2/PDU standard model is provided with a circuit breaker for connecting to the load or a
remote distribution cabinet. Other distribution configurations are available.
The three main types of distributions available for the STS2/PDU are:
• Output Breaker
• Inline Panelboards—two panelboards (84 poles) on 250A units and four panelboards (168 poles)
on 400-800A units. Square D
bolt-in or plug-in breakers.
• Square D I-Line
to 250A. Additionally, 300A to 400A breakers are available on 800A units.
For other optional distribution methods, contact your local Liebert representative or call
1-800-LIEBERT.
The STS2/PDU distribution may be mounted on either the right or left side at the customer's option.
Location of output conduit connections is affected by the location of the output cabinet. See
Figures 8, 9, 12, 13, 16 and 17 for wiring a right-side distribution configuration and
Figures 10, 11, 14, 15, 18 and 19 for wiring a left-side distribution configuration. See Figures 23
through 44 for wiring.
See Table 7 for wiring the various output options.
5.1

Customer Connections

The customer is responsible for connections from the STS2/PDU distribution to the connected load,
either directly or through remote distribution cabinets.
Table 7
Distribution configurations
Distribution Type
Output Breaker
250A
400-600A
800A
Inline Panelboards
250A
400-800A
I-Line (Square D)
W
IRING
®
and General Electric panelboards are available to accommodate
®
Panelboard—designed to accommodate up to 10 plug-in breakers from 100A
For Details See
Electrical Output
Field Connections
Figure 23
Figure 33
Figure 35
Figure 30
Figure 31
Figure 32
13

Output Power Wiring