Table 12 Event Messages - Liebert PDUTM Maintenance Manual

Liebert corporation operation & maintenance power supply sts2, pdutm
Table of Contents

Advertisement

Table 12
Event messages
ID
Alarm Message
1
S1 SCR SHORT
2
S2 SCR SHORT
3
S1 SCR OPEN
4
S2 SCR OPEN
5
PRIMARY FAN FAIL
6
CONTROL MODULE FAIL
7
PWR SPLY DC A FAIL
8
PWR SPLY DC B FAIL
9
PWR SPLY S1 AC FAIL
10
PWR SPLY S2 AC FAIL
11
PWR SPLY LOGIC FAIL
12
OUT VOLT SENSE FAIL
13
S1 VOLT SENSE FAIL
14
S2 VOLT SENSE FAIL
15
S1 SCR SENSE FAIL
16
S2 SCR SENSE FAIL
17
S1 CURR SENSE FAIL
18
S2 CURR SENSE FAIL
19
S1 GATE DRIVE FAIL
20
S2 GATE DRIVE FAIL
21
INTERNAL COMM FAIL
23
CB1 SHUNT TRIP FAIL
24
CB2 SHUNT TRIP FAIL
27
EQUIPMENT FAN FAIL
28
INPUT 1 SURGE FAIL
29
INPUT 2 SURGE FAIL
64
HEATSINK OVERTEMP
65
EQUIPMENT OVERTEMP
67
S1 UV
68
S1 UV (RMS)
69
S1 OV
70
S1 OF/UF
71
S1 FAIL
72
S2 UV
73
S2 UV (RMS)
74
S2 OV
75
S2 OF/UF
76
S2 FAIL
77
S1 OVERCURRENT
78
S2 OVERCURRENT
79
S1 I-PEAK
80
S2 I-PEAK
Description/Cause
One or more of the SCRs for Source 1 have shorted and failed.
One or more of the SCRs for Source 2 have shorted and failed.
One or more of the SCRs for Source 1 is open.
One or more of the SCRs for Source 2 is open.
A primary cooling fan has failed and the unit is now being cooled by a
secondary fan, which is not monitored.
Control logic module has failed.
Power supply DC bus A has failed.
Power supply DC bus B has failed.
Power supply Source 1 AC has failed.
Power supply Source 2 AC has failed.
A power supply module has failed.
The output volt sense module failed
The Source 1 volt sense module failed.
The Source 2 volt sense module failed.
The Source 1 SCR sense module failed.
The Source 2 SCR sense module failed.
The Source 1 SCR current module failed.
The Source 2 SCR current module failed.
The Source 1 gate drive module failed.
The Source 2 gate drive module failed.
Internal CAN communications failed.
CB1 shunt trip failed.
CB2 shunt trip failed.
One of the equipment fans failed
Source 1 input surge suppression module failed
Source 2 input surge suppression module failed
Heatsink has exceeded the recommended temperature.
Cabinet has exceeded the recommended temperature
Source 1 under voltage, fast detection.
Source 1 under voltage, slow detection.
Source 1 over voltage
Source 1 over frequency/under frequency
Source 1 failure.
Source 2 under voltage, fast detection.
Source 2 under voltage, slow detection.
Source 2 over voltage.
Source 2 over frequency/under frequency.
Source 2 failure.
Source 1 over current.
Source 2 over current.
I-PK on Source 1.
I-PK on Source 2.
85
Alarms and Faults
Action
D, F, A, E
D, F, A, E
D, F, A, E
D, F, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
D, F, A, E
D, F, A, E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sts2

Table of Contents