PDU Setpoints
The PDU Setpoints option allows you to configure the following parameters for the PDU, shown in
Figure 69.
• Load Voltage THD (%)
• Neutral Current (% of nom)
• Ground Current (A)
• Load Bus Overcurrent (% of nom)

Figure 69 PDU setpoints

Table 18 shows the range of valid values, default values and resolution for each parameter.
Table 18
PDU setpoints
Button
Load Voltage THD (%)
Neutral Current (% of nom)
Ground Current (A)
Load Bus Overcurrent (% of nom)
System Settings
The System Settings choice under the Config menu displays another pop-up menu with three choices:
• Comm Options
• System Options
• System ID
To access the System Settings menu:
1. Select CONFIG from the menu bar.
2. Select SYSTEM SETTINGS from the Config menu.
Range
Default
3.0% to 99.9%
15.0%
10% to 200%
95%
1.0A to 50.0A
5.0A
50% to 100%
100%
104