Liebert PDUTM Maintenance Manual page 150

Liebert corporation operation & maintenance power supply sts2, pdutm
Table of Contents

Advertisement

INPUT CONTACT #7
Input Contact Isolator #7
Occurrence of the indicated external event has been detected by Input Contact Isolator #7 of the Open Comms
Digital Input option board.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
The event, with its assigned name, was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
INPUT CONTACT #8
Input Contact Isolator #8
Occurrence of the indicated external event has been detected by Input Contact Isolator #8 of the Open Comms
Digital Input option board.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
The event, with its assigned name, was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
CONFIG MODIFIED
Configuration Modified
A setpoint has been updated and saved.
The event was written to the Event Log, if so configured.
PASSWORD CHANGED
Access Password Changed
The password for accessing the HMI (touch screen) options has been updated and saved.
The event was written to the Event Log, if so configured.
TIME REPROGRAMMED
System Time Reprogrammed
The system's time setting has been updated and saved.
The event was written to the Event Log, if so configured.
DATE REPROGRAMMED
System Date Reprogrammed
The system's date setting has been updated and saved.
The event was written to the Event Log, if so configured.
EVENT LOG CLEARED
Event Log Cleared
All past alarms and faults are no longer recorded in the system's event log.
This event was written to the Event Log, if so configured.
142
Event Message Help Text