Bryant Preferred 163A Installation Instructions Manual page 6

With puron r refrigerant 1--1/2 to 5 nominal tons (size 018 to 060)
Table of Contents

Advertisement

Accessory
Crankcase Heater
Evaporator Freeze Thermostat
Winter Start Control
Thermal Expansion Valve (TXV)
Hard Shutoff
Compressor Start Assist Capacitor and Relay
Low---ambient Pressure Switch
Support Feet
Liquid Line Solenoid Valve
* For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to the Longline
Guideline --- Air Conditioners and Heat Pumps using Puron refrigerant.
INSTALL LIQUID- -LINE FILTER DRIER INDOOR
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Installation of filter drier in liquid line is required.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Filter drier must be wrapped in a heat---sinking material
such as a wet cloth while brazing.
Refer to Fig. 5 and install filter drier as follows:
1. Braze 5- -in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5" liquid tube. Flow arrow
must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
Fig. 5 --- Liquid Line Filter Drier
Table 2—Accessory Usage
REQUIRED FOR LOW---AMBIENT
APPLICATIONS
(0°F To 55 °F)
Yes
Yes
(For non--- Evolution systems only)
Yes
(For non--- Evolution systems only)
Yes
Yes
Yes
(For non--- Evolution system only)
Recommended
No
REFRIGERANT TUBING CONNECTION OUTDOOR
Connect vapor tube to fitting on outdoor unit vapor service
valves (see Table 1.) Connect and braze the 3/8" coupling
(provided with the filter drier) to the liquid service valve and
connect and braze the liquid tubing to the other end of this
coupling. Use refrigerant grade tubing.
SWEAT CONNECTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service valves must be wrapped in a heat- -sinking
material such as a wet cloth.
Service valves are closed from factory and ready for brazing.
After wrapping service valve with a wet cloth, braze sweat
connections using industry accepted methods and materials.
Consult local code requirements. Refrigerant tubing and indoor
coil are now ready for leak testing. This check should include all
field and factory joints.
EVACUATE REFRIGERANT TUBING AND INDOOR
COIL
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. An alternate
triple evacuation method may be used if the deep vacuum
procedure is not followed.
IMPORTANT: Always break a vacuum with dry nitrogen.
A05178
6
REQUIRED FOR LONG LINE
APPLICATIONS* (Over 80 ft.)
Yes
No
No
Yes
Yes
No
No
See Long --- Line Application Guideline
CAUTION
CAUTION

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Preferred 165a

Table of Contents