  • Page 3: Table Of Contents

    RADION smoke Table of Contents | en Table of contents Introduction About documentation Bosch Security Systems, Inc. product manufacturing dates System overview Installation Installation guidelines Device testing Smoke test Sensitivity test Test/silence Maintenance Battery replacement Cleaning Limitations of smoke detectors Planning for emergencies Bosch Security Systems, Inc.
  • Page 4: Introduction

    Bosch Security Systems, Inc. product manufacturing dates Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/. The following image shows an example of a product label and highlights where to find the manufacturing date within the serial number.
  • Page 5: System Overview

    RADION smoke System overview | en System overview The RFSM-A smoke detector is designed to be used as a standalone smoke detector. The RFSM-A includes a built-in sounder for alarm alerts and a visual status LED. Figure 2.1: Detector features Callout ᅳ...
  • Page 6 1 every 45 +/- 2 seconds Sounder 85 dBA at 3m continuous RFI immunity 20 V/m minimum; 0-1000 MHz Compatibility To be used with B810 wireless receiver for UL approved applications 2013.09 | 02 | F.01U.280.752 Installation Guide Bosch Security Systems, Inc.
  • Page 7: Installation

    Notice! The detector cannot be attached to the mounting base if there are no batteries installed Test the RFSM-A. See Smoke test and Sensitivity test for more information. Bosch Security Systems, Inc. Installation Guide 2013.09 | 02 | F.01U.280.752...
  • Page 8: Installation Guidelines

    – In rooms with sloped, peaked, or gabled ceilings, install smoke sensors within 0.9 m (3 feet) measured down on the slant from the highest point of the ceiling. 2013.09 | 02 | F.01U.280.752 Installation Guide Bosch Security Systems, Inc.
  • Page 9 In dead air spaces at the top of a peaked ceiling or wall/ ceiling intersection. Dead air may prevent smoke from reaching a sensor. – Near flourescent light fixtures. Install sensors at least 3 m (10 feet) away from flourescent light fixtures. Bosch Security Systems, Inc. Installation Guide 2013.09 | 02 | F.01U.280.752...
  • Page 10: Device Testing

    A detector that fails to activate with the smoke test may require cleaning. If the sensor still fails to activate after cleaning, return the unit to Bosch for repair. Sensitivity test The sensor includes a sensitivity level test mode that lets you check the sensitivity using the test button and the LED as follows: Press and hold the test/silence button for 4 seconds, and then release it.
  • Page 11: Led

    The LED on the sensor (Figure 2.1) indicates the status of the sensor as follows: – Flashing – Flashes every 8 sec to indicate normal operation. – On – Detects smoke, sending an alarm. – Off – Trouble. Maintenance is required. Bosch Security Systems, Inc. Installation Guide 2013.09 | 02 | F.01U.280.752...
  • Page 12: Maintenance

    Figure 5.1: Remove the detector cap Squeeze the existing optical chamber where indicated (Figure 5.2) and pull it up and away from the sensor. 2013.09 | 02 | F.01U.280.752 Installation Guide Bosch Security Systems, Inc.
  • Page 13 Observing the proper polarity, install the batteries and the battery cover. The base will not fit properly if the batteries are not installed. Attach the sensor to the mounting base. Test the sensor sensitivity. See Sensitivity test for more information. Bosch Security Systems, Inc. Installation Guide 2013.09 | 02 | F.01U.280.752...
  • Page 14: Limitations Of Smoke Detectors

    2013.09 | 02 | F.01U.280.752 Installation Guide Bosch Security Systems, Inc.
  • Page 15: Planning For Emergencies

    – If you have children and/or physically challenged people residing in your household, use window decals to help emergency personnel identify the sleeping quarters of these individuals. Bosch Security Systems, Inc. Installation Guide 2013.09 | 02 | F.01U.280.752...
  • Page 18 Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450 www.boschsecurity.com © Bosch Security Systems, Inc., 2013...

Table of Contents