Horizontal Venting - Trane *UH2B060A9V3VA Installer's Manual

Upflow / horizontal and downflow / horizontal, gas-fired, direct vent, 2-stage condensing furnaces with variable speed inducer
Hide thumbs Also See for *UH2B060A9V3VA:
Table of Contents

Advertisement

Installer's Guide

HORIZONTAL VENTING

(Upflow/ Horizontal)
CAUTION
!
When the vent pipe is exposed to temperatures below
freezing, e.g., when it passes through unheated spaces, etc.,
the pipe must be insulated with 1/2 inch (22.7 mm) thick
Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then
the insulation will not be required. If domestic water pipes
are not protected from freezing then the space meets the
condition of a heated space.
NOTE: If your furnace comes with a factory supplied 2" X 3"
offset reducing coupling is used for 3" vent pipe installation,
make sure the marking "TOP" is located on the top side of
the pipe.
The straight side of the coupling must be on bottom for
proper drainage of condensate. See Figure 27.
Horizontal Venting
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200B
may be used in addition to the horizontal and vertical
termination options shown in the following figures.
Canadian applications ONLY: IPEX 196006 may be
used for horizontal and vertical terminations. IPEX
081216, IPEX 081218, and IPEX 081219 may only be
used for horizontal vent terminations.
9" MINIMUM
9" MINIMUM
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
20
Figure 27
For
Figure 28
9" MINIMUM
ELBOW AND TEE MUST
BE AS CLOSE TO-
GETHER
AS POSSIBLE
Figure 30
2" TO 3" COUPLING
#CPL00938
FACTORY SUPPLIED ONLY
WITH THE FOLLOWING
MODELS:
ALL 100,000 BTUH UPFLOW
MODELS, ALL 120,000 BTUH
UPFLOW MODELS, THE
UX1C080A9601 MODEL, AND
ALL DOWNFLOW MODELS
FURNACE
VENT
OUTLET
9" MINIMUM
9" MINIMUM
18-CD26D1-10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents