Gas Piping; Combustion And Input Check - Trane *UH2B060A9V3VA Installer's Manual

Upflow / horizontal and downflow / horizontal, gas-fired, direct vent, 2-stage condensing furnaces with variable speed inducer
Hide thumbs Also See for *UH2B060A9V3VA:
Table of Contents

Advertisement

Installer's Guide

Gas Piping

!
HAZARD OF EXPLOSION!
NEVER USE AN OPEN FLAME TO DETECT GAS LEAKS.
EXPLOSIVE CONDITIONS MAY OCCUR. USE A LEAK TEST
SOLUTION OR OTHER APPROVED METHODS FOR LEAK
TESTING. FAILURE TO FOLLOW RECOMMENDED SAFE LEAK
TEST PROCEDURES COULD RESULT IN DEATH OR SERIOUS
INJURY OR EQUIPMENT OR PROPERTY-ONLY-DAMAGE.
WARNING
!
HAZARD OF EXPLOSION
REPLACE AND/ OR TIGHTEN ALL PLUGS REMOVED OR
LOOSENED WHEN ADJUSTING GAS PRESSURE. LEAK
CHECK THE FITTINGS BEFORE PLACING THE FURNACE
INTO REGULAR SERVICE.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
FIRE, EXPLOSION, PROPERTY DAMAGE, OR DEATH.
WARNING
!
HAZARD OF EXPLOSION
DO NOT USE SEMI-RIGID METALLIC GAS CONNECTORS
(FLEXIBLE GAS LINES) WITHIN THE FURNACE CABINET.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
The upflow/horizontal furnace is shipped standard for left
side installation of gas piping. A knockout is provided on the
right side for an alternate gas piping arrangement. See Figure
54.
The installation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe joint
compound must be resistant to the chemical reaction with
liquefied petroleum gases.
Refer to piping Table 15, for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a manual
shut-off valve as shown in Figures 43 & 44. National codes
require a condensation drip leg to be installed ahead of the
controls as shown in Figures 55 & 56.
The furnace and its individual shut-off valve must be discon-
nected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa).
The furnace must be isolated from the gas supply piping by
closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE: Maximum pressure to the gas valve for natural gas
is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8" W.C. Mini-
mum pressure is 11.0" W.C.
Table 15
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
10
20
30
1/2
132
92
73
3/4
278
190
152
1
520
350
285
1-1/4
1050
730
590
This table is based on Pressure Drop of 0.3 inch W.C. and 0.6 SP.GR. Gas
32
WARNING
LENGTH OF PIPE
40
50
60
63
56
50
130
115
105
245
215
195
520
440
400
All gas fittings must be checked for leaks using a soapy solution
before lighting the furnace. DO NOT CHECK WITH AN
OPEN FLAME!
INPUT
RATING
BTUH
BURNERS
60,000
80,000
100,000
120,000

Combustion and Input Check

(See also High Altitude Derate, page 34)
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (deter-
mine the dial rating of the meter) for one revolution.
3. Match the "Sec" column in the gas flow (in cfh) Table 13
with the time clocked.
4. Read the "Flow" column opposite the number of seconds
clocked.
5. Use the following factors if necessary:
For 1 Cu. Ft. Dial Gas Flow CFH =
For 1/2 Cu Ft. Dial Gas Flow CFH =
For 5 Cu. Ft. Dial Gas Flow CFH =
6. Multiply the final figure by the heating value of the gas
obtained from the utility company and compare to the
nameplate rating. This must not exceed the nameplate
rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure
(See Table 17), or changing orifices (orifice change may
not always be required). To adjust the manifold pres-
sure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tubing to
the outlet pressure boss marked "OUT P" on White-
Rodgers gas valve model 36G or 36J. See Figure 57A for
White-Rodgers gas valve model 36J. See Figure 57B for
White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set screw
one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611)
contains a 3/32" hex wrence, a 5/16" hose and a
connector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
70
46
96
180
370
Table 16
ORIFICE SIZES
MAIN BURNER ORIFICE
NUMBER
DRILL SIZE
OF
NAT. GAS
3
45
4
45
5
45
6
45
Chart Flow Reading ÷ 2
Chart Flow Reading ÷ 4
10X Chart Flow Reading ÷ 4
LP GAS
56
56
56
56
18-CD26D1-10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents