Horizontal Venting - Trane UC1B040A9241A series Installer's Manual

Upflow/ horizontal and downflow/ horizontal gas-fired condensing furnaces
Hide thumbs Also See for UC1B040A9241A series:
Table of Contents

Advertisement

k
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS

HORIZONTAL VENTING

NOTE:
Vent
termination
kit
BAYVENT200B may be used instead of the horizontal
and vertical termination options shown in the follow-
ing figures.
!
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces,
etc., the pipe must be insulated with 1/2 inch (22.7 mm)
thick Armaflex-type insulation or equal. If the space is
heated sufficiently to prevent freezing, then the insula-
tion would not be required. If domestic water pipes are
not protected from freezing then it is assumed the
space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as
shipped) or as nondirect vent. Installation must
conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation
level.
Avoid areas where staining or condensate drippage may
be a problem.
18-CD19D5-25
BAYAIR30AVENTA*
CAUTION
Installer's Guide
ELBOW AND TEE MUST BE
AS CLOSE TOGETHER
AS POSSIBLE
Location of the vent/ wind terminal should be chosen to
meet the requirements of Figure 27 for either direct or
non-direct vent applications.
or
l
3.2"
COMBUSTION
AIR
ANCHORS
(4 req.)
VENT
PLATE
VENT
12" MINIMUM
TO OVERHANG
VENT
VENT
CAP
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
BAYVENT200B
SCREWS
(4 req.)
21