Mitsubishi city multi PKFY-08NAMU-A Technical & Service Manual page 51

Split-type, heat pump air conditioners
Table of Contents

Advertisement

OPERATING PROCEDURE
(7) Remove the indoor controller board case.
Then the Power board and the capacitor can be serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the terminal cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
6. Removing the intake grilles
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side.
(See Figure 3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely
(3) Remove the air filters.
(4) Hold and press the center cover to remove.
(5) Remove the screws of the grilles.
(6) Pull the lower side of the grille toward you and slide the
upper to the right to remove the grilles.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical parts box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Photo 3
Power board
Terminal block
Photo 4
Figure 3
Photo 5
Left side panel
Photo 6
OC292-49
PHOTOS & ILLUSTRATION
Indoor controller board
Screws
Vane motor
Catch on the left side panel
Catch on
the unit
Slide to the
right
Screws for grilles
Drain pan
Screws
Capacitor
Electrical
parts box
Grills
Drain hose
band
Drain hose

Hide quick links: