Troubleshooting - Mitsubishi city multi PKFY-08NAMU-A Technical & Service Manual

Split-type, heat pump air conditioners
Table of Contents

Advertisement

9

TROUBLESHOOTING

9-1. How to check
PKFY-08NAMU-A
Part Name
Room temperature
Disconnect the connector, then measure the resistance using a tester.
thermistor(TH21)
(Surrounding temperature 50˚F~86˚F)
Liquid pipe temperature
thermistor(TH22)
Gas pipe temperature
thermistor(TH23)
1Measure the resistance between the terminals using a tester.(Surrounding temperature 77˚F.)
Vane motor
3
Blue
M
5
Yellow
Red
1
Orange Pink
Connect pin No.
4
2
Fan motor
1Measure the resistance between the terminals using a tester.(Surrounding temperature 68˚F.)
FAN
1
White
Red
4
2Without disassembling the parts, measure the electrical pressure of the gray wire(Signal line) and
Black
6
Fuse
293I4°F
Brown
Gray Yellow
3
2
1
CN34
Linear expansion
Disconnect the connector then measure the resistance valve using a tester.
valve
(Coil temperature 68˚F)
Blue
4
Brown
6
M
White-Red
2
Yellow
5
3
1
White
Red
Orange
Normal
Abnormal
4.3k
~9.6k
Open or short
'
'
Normal
1-2
1-3
Red-Pink
Red-Blue
400'
White-Black
Red-Black
brown wire (GND) while the power is on.
!At first, check if the electrical pressure is 12V between the
brown wire(GND) and yellow wire(VCC).
Normal
@Slowly start running the fan. It is normal if while the fan rotate once,
the electrical pressure change from 0V to12V then go back to 0V.
If the electrical pressure stay at around 0V or 10V, it means the fan
Abnormal
motor has the defects.
Normal
1-5
2-6
Yellow-Brown
150'
OC292-33
Check points
(Refer to page OC292-36 for details.)
1-4
1-5
Red-Orange
Red-Yellow
± 7%
Normal
195'
200'
3-5
4-6
Orange-Red
Blue-Brown
±10%
Abnormal
Open or short
Abnormal
Open or short
Abnormal
(Refer to page
OC292-36 for details.)
Open or short