8-2. DRY operation

Control modes
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
1. Thermoregulating
function
room temperature (TH1).
1-2. Frozen prevention control
2. Fan
Indoor fan operation controlled depends on the compressor conditions.
Note: Remote controller setting is not acceptable.
3. Drain pump
Same control as COOL operation
Except for
PKFY-08NAMU-A.
4. Vane
Same control as COOL operation
(up/ down vane change)
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display DRY.
3 Press the SET TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the
Setting the Dry thermo by the thermoregulating signal and the
Dry thermo ON Room temperature ] desired temperature + 2°F
Dry thermo OFF Room temperature [ desired temperature
3 min. passed since starting operation
Room
temperature
Thermoregulating signal Room temperature (T1)
ON
Over 64°F
OFF
Less than 64°F
No control function
Dry thermo
Fan speed notch
[Low]
ON
OFF
Stop
OC292-27
pressed one time. Dry 67 to 87°F.
Control details
T1 ] 82°F
82°F > T1 ] 79°F
79°F > T1 ] 75°F
75°F > T1
Unconditional
Dry thermo OFF
or
Dry thermo
Dry thermo
ON
OFF
time (min)
time (min)
9
3
7
3
5
3
3
3
3
10