Operation Data - Toshiba RAS-B16N3KV2-E Service Manual

Split type
Hide thumbs Also See for RAS-B16N3KV2-E:
Table of Contents

Advertisement

7-2. Operation Data

<Cooling>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
B16N3KV2-E
27/19
35/-
<Heating>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
B16N3KV2-E
20/-
7/6
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Heat exchanger
Standard
pipe temp.
pressure
P (MPa)
T1 (°C)
0.8 to 1.0
11 to 13
Heat exchanger
Standard
pipe temp.
pressure
P (MPa)
T1 (°C)
2.7 to 2.9
43 to 45
20
FILE NO. SVM-12061
Indoor
fan mode
T2 (°C)
40 to 42
High
Indoor
fan mode
T2 (°C)
0 to 2
High
Outdoor
Compressor
fan mode
revolution
(rps)
High
71
Outdoor
Compressor
fan mode
revolution
(rps)
High
72