Indoor Fan Motor Control - Toshiba RAS-B16N3KV2-E Service Manual

Split type
Hide thumbs Also See for RAS-B16N3KV2-E:
Table of Contents

Advertisement

Item
2. Indoor fan
<In cooling operation>
motor control
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
COOL ON
Fan speed setup
AUTO
Ta
[ ˚C ]
+2.5
a
+2.0
b
+1.5
c
+1.0
d
+0.5
e
Tsc
(Table 1) Indoor fan air flow rate
Fan speed
level
WF
WE
WD
WC
WB
WA
W9
W8
W7
W6
W5
W4
W3
W2
W1
Operation flow and applicable data, etc.
MANUAL
Indication
L
L+
M
M+
H
Air volume AUTO
M+(WB)
*3
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*4
*5
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
L(W6)
from M+ and L)
RAS-B16N3KV2- E
COOL HEAT DRY
Fan speed
(rpm)
UH
1510
H
1510
UH
UH
M+
1480
H
H
1430
M
M+
M+
1280
M
1220
M
L+
1150
L
1000
L+
L-
L+
980
L
L
920
L-
UL
L-
900
UL
UL
840
SUL
SUL
770
SUL
620
520
(Fig. 1)
Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
Air flow rate
(m3/h)
735
735
717
686
594
557
514
421
409
372
360
323
280
187
126
27
FILE NO. SVM-12061
Description
* Symbols
UH
: Ultra High
H
: High
M+
: Medium+
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.