Installing Basic Wall Sleeve; Frame And Brick Wall Construction Type - Daikin McQuay IM 934-5 Installation & Maintenance Data

Pdaa dual motor angled top unit - 16" x 42" with r-410a refrigerant applied packaged terminal air conditioner
Table of Contents

Advertisement

Installing Basic Wall Sleeve

Frame and Brick Wall Construction Type

A heavy-gauge, corrosion resistant wall sleeve is provided
for each unit. The wall sleeve is either shipped in a separate
carton or shipped in a multipack of 15.
The basic wall sleeve is designed to be easily installed in a
variety of wall constructions.
Note: The center of gravity is 10" (254mm) from the rear
face of the wall sleeve. The wall sleeve must be
inserted into the wall at least 10" (254mm) or other
support must be employed.
Support can be from a factory supplied subbase or from
other field supplied materials. Recommended installation
procedures are described below
1. Clean the opening of all debris that may interfere with
installation.
2. If the unit is to be supplied with a subbase, install
subbase before installing wall sleeve (see
3. lf the optional drain kit is to be employed, see
Condensate Drain Kit(s)" on page 11.
4. Place a thin pad of soft mortar on the bottom of the
opening and slide in the wall sleeve. Be sure to recess
the wall sleeve enough to accommodate outside louver.
This recess is 3/8" (9.5mm) for stamped louvers and 1
(32mm) for architectural louvers. Louver should be flush
to exterior surface when complete.
Note: The wall sleeve is not intended to replace the lintel.
5. Level wall sleeve left to right and pitch 1/4" front to
back, pitch to the outside. Secure by anchoring with
appropriate fasteners. A 5/16" (8mm) hole is provided on
each side, 2" (51 mm) down from the top and 2" (51mm)
in from the rear of the wall sleeve. Additional holes may
be required to firmly secure the wall sleeve. Refer to
Figure
16.
CAUTION
DO NOT drill holes in the bottom of the wall sleeve as it will
cause leaks.
6. Where a subbase is used, secure wall sleeve to subbase
with clips provided.
7. Caulk the wall sleeve to the wall opening on both the
inside and outside perimeter. Be careful not to plug the
weep holes. Caulking should be resilient, nonhardening
type such as silicone.
IM 934-5
(see Figure 17 -
19).
IM
936-x).
"Installing
1
Figure 17: Frame and brick with electrical subbase
Outside
Louver
Mounting
Holes
(by installer)
Caulk Perimeter
both Indoor and
Outdoor Before
Installing Louver
Note: Standard subbase is available in 3" or 4" (76 mm or
102 mm) height. Leveling legs provide adjustment of
1" (25 mm).
/
"
Figure 18: Frame and brick with cord connection
4
Mounting
Screws
by Installer
Outdoor
Louver
Caulk Perimeter
Steel Lintel
(by others)
/
3
4
"
8
(111mm)
/
3
13
"
4
(349mm)
8
/
1
"
4
(209mm)
16"
(406mm)
Room
Wall Sleeve
Cabinet
Subbase
See Note
Leveling Leg
Power Supply Connect
(Alternate Entry)
Steel Lintel
(by others)
/
13
3
"
4
8
/
1
"
(349mm)
4
(209mm)
16"
(406mm)
Room
Wall Sleeve
Cabinet
3" Min. (76mm)
Wall Receptacle
Finished Floor
(by others)
Page 15 of 48
17"
(432mm)
Finished Floor
or Top
of Carpet
17"
(432mm)
or Carpet