Installation Requirements; Minimum Room Height - Viessmann VITOCAL 222-G Technical Manual

Compact heat pumps 5.9 to 10.3 kw
Hide thumbs Also See for VITOCAL 222-G:
Table of Contents

Advertisement

Design information
(cont.)

11.2 Installation requirements

■ The installation room must be dry and free from the risk of frost.
■ The appliance can be installed near (but not in) the living space.
Subject to the structure of the installation room, e.g. sound-
reflecting (tiled) walls or ceilings, additional sound insulation
measures may be required on site to reduce the structure-borne
and air-borne noise.
■ We recommend you never install this device on wooden floors in
attics to prevent the transmission of structure-borne noise.
■ The doors of the installation room should correspond to at least
emission protection category E1. This is usually achieved by fitting
tubular chipboard doors.

Minimum room height

! Without pre-assembly connection set
? With pre-assembly connection set
A Compact heat pump
B Top edge of finished floor or top edge of platform for unfinished
floors
Vitocal 222-G/333-G
Vitocal 242-G/343-G
VITOCAL
Dimension a in mm
1829
2075
■ Provide corresponding installation areas for accessories and expan-
sion vessels on the brine side.
■ Carry out the diffusion-proof thermal insulation on the brine side of
the heat pump installation in accordance with standard practice to
prevent condensation.
■ Due to its heavy total weight, the appliance must be installed on a
separate anti-vibration concrete platform or on the platform for unfin-
ished floors (accessory).
C Connection panel from pre-assembly connection set
a
Compact heat pump height
h
Minimum room height
Recommended minimum room height h in mm
! without connection set
2000
2250
11
? with connection set
2100
2350
VIESMANN
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents