Control unit accessories
On-site requirements:
■ Telephone connection
– Type FA5:
TAE socket, coding "6N"
– Type FI2:
RJ45 socket (ISDN)
■ Type GP2:
Adequate GPRS radio signal for the D2 [Vodafone] mobile network
at the location where the Vitocom 300 is installed
■ LON communication module must be installed in the Vitotronic appli-
ance
Note
For further information regarding the terms of contract, see the
Viessmann pricelist.
Standard delivery:
■ Standard module
*19
(with 8 digital inputs, 1 digital output and 2 ana-
logue sensor inputs)
– Type FA5:
with integral analogue modem,
Connecting cable for telephone socket TAE 6N, 2 m long
– Type FI2:
with integral ISDN modem,
Connecting cable with RJ45 plug for ISDN socket, 3 m long
– Type GP2:
with integral GPRS modem,
Aerial with connecting cable, 3 m long
SIM card
■ LON connecting cable RJ45 – RJ45, 7 m long, for data exchange
between the Vitotronic and Vitocom 300
■ Power supply unit
*19
■ Power cable from the power supply unit to the standard module
Note
For standard delivery of packs with Vitocom, see pricelist.
Accessories:
Accessories
Wall mounting enclosure for the installation of the
Vitocom 300 module, if no control panel or electrical
distribution panel is available
2 rows
3 rows
*19
Extension module
13
– 10 digital inputs (8 zero volt, two 230 V~)
– 7 analogue inputs (2 can be configured as pulsed
inputs)
– 2 digital outputs
– see the standard module for dimensions
or
– 10 digital inputs (8 zero volt, two 230 V~)
– 7 analogue inputs (2 can be configured as pulsed
inputs)
– 2 digital outputs
– 1 M BUS interface with connection of up to, for exam-
ple, 16 M BUS capable heat meters with M BUS slave
interface to EN 1434-3
– see the standard module for dimensions
Uninterruptible power supply unit
Additional rechargeable battery pack
– Recommended with 1 basic module, 1 extension
module and all inputs allocated
– Required with: 1 standard module and 2 extension
modules
*19
Mounting rail installation TS35 to DIN EN 50 022, 35 x 15 and 35 x 7.5.
VIESMANN
80
(cont.)
Part no.
7143 434
7143 435
7143 431
7159 767
*19
7143 432
(UPS)
*19
for UPS
7143 436
Accessories
Extension of the connecting cable
Installation spacing 7 to 14 m
– 1 connecting cable (7 m long)
and
1 LON coupling RJ45
Installation spacing 14 to 900 m with plug-in connec-
tor
– 2 LON plug-in connectors RJ45
and
– 2-core cable, CAT5, screened, solid cable, AWG
2
26-22, 0.13 to 0.32 mm
, external diameter,
4.5 to 8 mm
or
2-core cable, CAT5, screened, wire, AWG 26-22,
2
0.14 to 0.36 mm
, external diameter, 4.5 to 8 mm
Installation spacing 14 to 900 m with socket
– 2 connecting cables (7 m long)
and
– 2 LON sockets RJ45, CAT6
– 2-core cable, CAT 5, screened
or
JY(St) Y 2 x 2 x 0.8
Standard module (standard delivery):
0
1 6
9 0
Specification
Rated voltage
Rated current
– Type FA5
– Type FI2
– Type GP2
Protection class
IP rating
Function
Permissible ambient temperature
– during operation
– during storage and transport
On-site connections:
– 8 digital inputs DE 1 to DE 8
– 1 digital output DA1
– 2 analogue inputs AE 1 and AE 2
Part no.
7143 495
and
7143 496
7199 251
and
on-site
or
on-site
7143 495
and
7171 784
on-site
or
on-site
24 V –
600 mA
500 mA
500 mA
II to DIN EN 61140
IP 20 to EN 60529;
ensure through appropriate
design/installation
Type 1B to
EN 60730- 1
0 to +50 °C
Installation in living spaces
or boiler rooms (standard
ambient conditions)
-20 to +85 °C
Zero volt contact, 2-pole,
24 V–, max. 7 mA
Zero volt relay contact, 3-
pole, changeover, 230 V~/
30 V–, max. 2 A
For Viessmann Ni500 tem-
perature sensors, 10 to 127
ºC ±0.5 K
VITOCAL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents