INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH DIRECT-VENT GAS FIREPLACES (DRT63STTEN/P) • INSTALLATION INSTRUCTIONS

Gas Supply Pressure Requirements

Inlet and manifold gas supply pressure require-
ments for these appliances are listed in Tables
2 and 3.
Inlet Gas Supply Pressure (all models)
Fuel #
Minimum
5.0" WC
Natural Gas
(1.24 kPa)
11.0" WC
Propane
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure (all models)
Fuel #
Low
Natural
(Lo) 1.6" WC
Gas
(0.4 kPa)
(Lo) 6.3" WC
Propane
(1.57 kPa)
Table 3
Test gauge connections are provided on
the front of the electronic gas control valve
(identified IN for the inlet and OUT for the
manifold side).
The control valves have a 3/8" (10 mm) NPT
thread inlet and outlet side of the valve. Refer
to Figure 1.
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step-down regulators to reduce the
pressure to safe levels.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
(From DFC Wire
Manifold (Out)
Test Port
Line (In) Test Port
Orange Wire
(from DFC Wire
Harness)
Inlet
3/8" NPT
Figure 1: SIT Proflame Valve
6
These appliances must be isolated from
the gas supply piping system (by closing
their individual manual shut-off valve)
during any pressure testing of the gas
supply piping system at test pressures
equal to or less than 1/2 psig (3.5 kPa).
Maximum
10.5" WC
These appliances and their individual
(2.61 kPa)
shut-off valves must be disconnected
13.0" WC
(3.23 kPa)
from the gas supply piping system
during any pressure testing of that
system at pressures greater than 1/2
psig (3.5 kPa).
High
(Hi) 3.5" WC

Orifice Sizes

(0.87 kPa)
(Hi) 10.0" WC
Sea Level To High Altitude (All Models)
(2.49 kPa)
These appliances are tested and approved
for installation at elevations of 0–4500 feet
(0– 1372 meters) above sea level using the
standard burner orifice sizes (marked with an
asterisk [*] in Table 4 ). For elevations above
4500 feet, contact your gas supplier or qualified
service technician.
Deration
At higher elevations, the amount of BTU fuel
value delivered must be reduced by either:
• using gas that has been derated by the gas
company; or
• changing the burner orifice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CSA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
Green Wire
Harness)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
54 / ANSI Z223.1 - latest edition or , in Canada,
the CAN/CSA-B149.1- latest edition.
Table 4

Gas Valve Diagram

See valve diagram in Figure 1.
COMMONWEALTH OF MASSACHUSETTS
REQUIREMENTS
These appliances are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
• Installation and repair must be done by a
• The flexible gas line connector used shall
• The individual manual shut-off must be a
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements::
• A hard-wired carbon monoxide detector
Connect GTMS
Wire Harness
Pressure
• A metal or plastic identification plate must
Regulator
Tower
Outlet
3/8" NPT
Yellow Ground Wire
(From DFC Wire
Harness)
New York City, New York (MEA)
Installation of these fireplaces is approved for
installation in New York City, NY.
NOTE: Flame appearance will diminish
4% per thousand feet.
Burner Orifice Sizes
Elevation 0 –4500 feet (0 –1372 meters)
Natural Gas
Propane
Drill size (inches)
Drill size (inches)
#32 (0.116")*
#52 (0.0635")*
H8002 •
H8003 •
*
Standard size installed at factory.
• Part/Catalog Number.
Massachusetts Rules and Regulations 248
C.M.R. Sections 4.00 through 8.00.
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
not exceed 36 inches (92 centimeters) in
length..
T-handle type valve.
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified.
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.