Samsung AVXCSH023/032/040CE Service Manual page 309

System air conditioner indoor unit outdoor unit
Table of Contents

Advertisement

PCB Diagram
■ BLCD
CN701-Power Input (AC220V)
38
#1: L
#3: N
CN101- Motor Control Signal
42
#1: U Phase Control Signal
#2: DC 5V #3: V Phase Control Signal
#4: GND
#5: W Phase Control Signal
#6: Motor Temp. Sensor Input
#7: GND
6-29
BD701
WHT
GT2
CN703
BLK
CN701
BLU
2
L601
AC220~240V
C604
R604
C605
ZD601
LD601
Y-GRN
PTC2
PTC1
D601
C611
C613
C612
LD602
R608
D603
C614
R813
LD801
RED
R206
FAN/RPM
R208
R811
REV/OUT
O/TEMP
IC101
C810
O/CURRENT
R808
INRUSH
R809
FAN
IC202
IPMFAULT
GND
R511
VCC 5V
R509
12V
R510
C102
R504
PC504
GT2-Trans Output
39
#1: AC 220V - L
#2: AC 220V - N
CN31- Motor Power
43
#1: U Phase Output
#2: V Phase Output
#3: W Phase Output
CN301
WHT
C701
C702
C312
R405
C606
C403
R404
5
W
V
U
R605_FUSIBLE
IC601
2 7
2 1
C602
C401
R402
C402
R403
R603
R401
C601
C201
R203
IC301
R202
D602
R201
C202
R205
7805
R204
1
2 0
R609
LD603
Y-GRN
C304
C305
C306
XT801
R814
R807
IC801
D301
D302
D303
C808
C309
C809
C301
C302
C303
R806
DVMPLUS3
C307
C806
C807
BLDC-DRIVER
R802
R803
DB41-00637A
R801
C805
070626-00437-03
C801
C802
08.01.04
C803
CN101
R805
WHT
R804
CN703- Power Output (220V)
40
#1: AC 220V - L
#3: AC 220V - N
C311
41
CN501- Main PCB Signal
Connector
#1: 12V Input
#2: 5V Input
#3: GND
#4: IPM Fault Error Signal Output
#5: Fan Control Signal Input
#6: Inrush Relay Movement Signal Input
#7: Motor Over Voltage Detection
Signal Output
#8: Motor Overheating detection
Signal Output
#9: Motor Counter Rotation Detection
Signal Output
#10: Motor RPM Feedback Signal
#11: Not used
#12: Not used
#13: Not used
Samsung Electronics