Troubleshooting
4-3-27 Compressor's Discharge Temperature Sensor dislocation error
1. How to check
Are a discharge sensor and
a sensor holder securely attached?
Does the compressor
operate well and is the temperature
of discharge piping for compressor kept at
certain temperature
Is the resistance value
for the sensor appropriate?
Restart then check again
4-66
Yes
level?
Yes
Yes
No
Reinsert the sensor
Re-attach the sensor holder
No
Analyze the cause of the compressor's
failure to operate
No
Defective sensor
Replace the sensor
Samsung Electronics