Studer XP-COMPACT-XPC 1400-12 User's And Installer's Manual page 13

Sine wave inverter, battery charger, transfersystem
Table of Contents

Advertisement

Available languages

Available languages

STUDER Innotec
XP-COMPACT
2.5mm2). Connections are marked as follows "N" Neutral, "PE" Earth (connected to
the appliance enclosure), "L" Live.
Caution: High voltages can be there. Make sure that the XP-COMPACT is
turned off (LED 13 lighting) before the connection.
3.6.3 Connection to the 230Vac Input (AC INPUT)
The 230V-supply from network or from a generator must be connected to the input
terminals AC INPUT with cables which cross section depends on the power source
(usually 2.5mm2). Connections are marked as follows: "N" Neutral, "PE" Earth
(connected to the appliance case), "L" Live.
3.6.4 Connect the solar modules: SOLAR +/- (Only for solar option)
Solar modules are connected on these terminals. Under no circumstances should
any other energy source i.e. wind generator be connected to these terminals! Only
solar modules must be connected with two cables +/-. Depending on the power of the
modules, the cable cross section should be 2.5 up to 6mm2. Before connecting it is
necessary to check with a Voltmeter that the voltage of the Module meets the
following values:
XPC 1400-12 17-25V/30A, XPC 2200-24 34 – 45V/30A, XPC 2200-48 68 – 90V/20A.
3.6.5 Connection to Auxiliary Contact
This contact is a potential free change over contact the currents and voltages allowed
for this contact are max. 16A/250Vac. The LED 5 "Contact active" shows the position
of them: alight mind active and off mind non-active. The schematic view of the
connections on the front, show the relay in the non-active mode.
3.6.6 Connection to Remote control
The Remote Control RCC-01 is connected in the terminal marked „Remote control"
with a 20m long cable and a RJ11/8 connector. The Remote Control can be plugged
IN or plugged OUT during any operation situation. Push in the connector softly until
you hear the „click" showing that the connector is locked. The same applies to the
plug in the Remote Control.
The length of the cable for Remote Control should not exceed 40m. We deliver it with
20m cable.
3.6.7 Connection to Temperature Sensor (Temp.)
The temperature sensor CT-35 is connected in the terminal marked „Temp" with a
3m long cable and a RJ11/6 connector. The temperature sensor can be plugged IN
or plugged OUT during any operating situation. Push in the connector softly until you
hear the „click" showing that the connector is locked. The temperature sensor must
be glued to the wall of the battery or near it. The Temperature Sensor cable must
not be tied together with the battery cables or laid in a rope/bundle.
XP-COMPACT V5.7
13/79