Viessmann VITOTRONIC 100 Installation And Service Instructions Manual page 51

Type gc1 digital boiler control unit
Table of Contents

Advertisement

System version 17
Codes must be set on every Vitotronic 100.
Required coding
01 : 2
Multi−boiler system with cascade control via LON BUS
01 : 3
Multi−boiler system with external cascade control via switching
contacts
02 : 2
Modulating burner operation
03 : 1
Only with Vitotronic 100 for low temperature boilers:
Oil fired operation (irreversible)
0C : 1 Only with Vitotronic 100 for low temperature boilers:
Constant return temperature control
0d : 0
Only with Vitotronic 100 for Vitocrossal 300:
Without Therm−Control
4d : 2
Only with Vitotronic 100 for low temperature boilers:
Boiler circuit pump on plug sL
Automatic changeover
4A: 1
Only with Vitotronic 100 for low temperature boilers:
Connecting temperature sensor T1 to plug aJA
*1
If required.
(cont.)
*1
*1
Heating system designs
51