Viessmann VITOTRONIC 100 Installation And Service Instructions Manual page 114

Type gc1 digital boiler control unit
Table of Contents

Advertisement

Troubleshooting
Faults which are displayed at the programming unit
Fault
System
code
characteristics
Cylinder primary
58
pump ON:
Set cylinder water
temperature = set
boiler water
temperature,
priority control is
cancelled
or
With cylinder
storage system:
Cylinder heating is
started and stopped
by cylinder temp.
sensor 2
With cylinder
59
storage system:
Cylinder heating is
started and stopped
by cylinder temp.
sensor 1
Boiler at maximum
60
temperature,
no output reduction,
return control OFF
68
Shunt pump
70
constantly ON
With cylinder
storage system:
storage system:
78
Mixer primary
circuit closed, no
DHW heating
114
Cause
Lead broken
Cylinder temp.
sensor 1
Lead broken
Cylinder temp.
sensor 2
Short circuit
Temperature sensor
aJA
p
,
Lead broken
Temperature sensor
aJA
Short circuit
Temperature sensor
aJB
Lead broken
Temperature sensor
aJB
(cont.)
Remedy
Check cylinder temp.
sensor
(see page 130)
Check temperature
sensor
(see page 131).
(
p g
)
Without
temperature sensor
Set code "4A:0"
Check temperature
sensor
(see page 131).
Without
Without
temperature sensor
Set code "4b:0"