Viessmann VITOTRONIC 100 Installation And Service Instructions Manual page 149

Type gc1 digital boiler control unit
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
General
76 :
0
Without communication
module
77 :
1
LON user number
78 :
1
Enable LON communication 78 :
79 :
0
Control unit is not fault
manager
80 :
1
A fault message is
displayed, providing a fault
is active for at least 5 s
Temperature displayed in ºC
88 :
0
(Celsius)
8A : 175
Do not adjust
92 : 160
Do not adjust
Address will only be displayed if "8A : 176" has been programmed.
93 :
0
Emissions test function and
service indication do not
affect central fault messages
94 :
0
Without plug−in adaptor for
external safety equipment
Possible change
76 :
76 :
77 :
to
77 : 99
79 :
g
80 :
80 :
to
80 : 199
88 :
93 :
94 :
1
With LON communication
module;
will be recognised
automatically
2
Do not adjust.
2
LON user number,
adjustable from 1 to 99
Note
Allocate each number only
once.
0
Disable LON
communication
1
Control unit is fault
manager
0
Immediate fault message
2
The minimum fault
duration before a fault
message is issued, is
adjustable from 10 to 995 s;
1 step ¢ 5 s
Temperature displayed in ºF
1
(Fahrenheit)
1
Emissions test function/
service indication does
affect central fault
messages
1
With plug−in adaptor for
external safety equipment;
will be recognised
automatically
Coding