Type gc1 digital boiler control unit
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
DHW (cont.)
61 :
1
The cylinder primary pump
starts immediately
62 : 10
The cylinder primary pump
will run on for a max. of
10 min
63 :
0
Without auxiliary function
for DHW heating
67 : 40
With Vitosolic:
Third set DHW temperature
at 40 ºC. Reheating will be
suppressed above the
selected temperature. The
DHW cylinder is heated
exclusively by the solar
heating system.
68 :
8
With 2 cylinder temperature
sensors (coding "55 : 2"):
cylinder heating switch−off
point with set value × 0.8
69 :
7
With 2 cylinder temperature
sensors (coding "55 : 2"):
cylinder heating starting
point with set value × 0.7
148
Possible change
61 :
62 :
62 :
to
62 : 15
63 :
g
63 :
to
63 : 14
63 : 15
67 :
p
67:
to
67 : 95
68 :
to
68 : 10
69 :
to
69 :
0
The cylinder primary pump
will be switched ON subject
to the boiler water
temperature
0
Cylinder primary pump
without run−on
1
Run−on time adjustable
from 1 to 15 min
Additional function:
1
1 × daily
2
every 2 days
to
every 14 days
2 × daily
0
Without a third set DHW
temperature
1
Input of a third set DHW
value; adjustable from
1 to 95 ºC (subject to the
setting of coding
address "56")
2
Factor adjustable
from 0.2 to 1;
1 step ¢ 0.1
1
Factor adjustable
from 0.1 to 0.9;
1 step ¢ 0.1
9