Viessmann VITOTRONIC 100 Operating Instructions Manual

Viessmann VITOTRONIC 100 Operating Instructions Manual

Heating system with control unit for operation with a constant boiler water temperature

Advertisement

Quick Links

Operating instructions
for the system user
Heating system with control unit for operation with a constant boiler water
temperature
Vitotronic 100, type CC1E
Vitotronic 100, type CC1I
VITOTRONIC 100
5798 582 GB
3/2017
VIESMANN
Please keep safe.

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITOTRONIC 100

  • Page 1 VIESMANN Operating instructions for the system user Heating system with control unit for operation with a constant boiler water temperature ■ Vitotronic 100, type CC1E ■ Vitotronic 100, type CC1I VITOTRONIC 100 Please keep safe. 5798 582 GB 3/2017...
  • Page 2 Safety instructions For your safety Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained Danger Note This symbol warns against the risk of injury. Details identified by the word "Note" contain additional information. Please note This symbol warns against the risk of material losses and environmental pollution.
  • Page 3: Safety Instructions

    Safety instructions For your safety (cont.) If you smell gas Danger Escaping gas can lead to explosions which may result in serious injury. ■ Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appli- ances on or off. Close the gas shut-off valve.
  • Page 4 Safety instructions For your safety (cont.) Installation room requirements Danger Please note Sealed vents result in a lack of combustion air. Incorrect ambient conditions can lead to heating This leads to incomplete combustion and the system damage and can put safe operation at formation of life threatening carbon monoxide.
  • Page 5 Scanning fault messages ............... 21 Calling up a fault message ..............21 ■ Burner faults ..................22 ■ 7. Emissions test mode ........................ 23 8. Switching on and off Control unit controls ................24 Vitotronic 100, type CC1E ..............24 ■...
  • Page 6 Index Index (cont.) Vitotronic 100, type CC1I ..............24 ■ Shutting down the heating system ............24 With frost protection monitoring ............24 ■ Without frost protection monitoring (shutdown) ........24 ■ Starting up the heating system .............. 25 9. What to do if...
  • Page 7: Introductory Information

    This information can be found in chapter "Terminology" in the Appendix. Intended use The device is intended to control only Viessmann Incorrect usage or operation of the appliance (e.g. the medium sized and industrial/commercial boilers with oil appliance being opened by the system user) is prohibi- or gas burners, in line with the intended use of those ted and will result in an exclusion of liability.
  • Page 8: Your System Is Preset

    Introductory information Product information The Vitotronic 100, type CC1E and type CC1I control Note units are designed for the control of single boiler sys- Alternatively, your heating contractor can configure the tems with a constant boiler water temperature. Vitotronic control unit as a "Boiler in the Cascade":...
  • Page 9: Operating Principles

    Remote control operating instructions ■ By means of a Viessmann app, you can operate the control unit via your smartphone. Home screen: Displays and settings The home screen provides you with the most fre- Call up the home screen as follows: quently used settings and queries.
  • Page 10 Control unit operation Home screen: Displays and settings (cont.) Symbols: Entry or selection confirmation In conjunction with a solar thermal system: Help text call-up Solar circuit pump is running Menu scrolling Burner (gas or oil) in operation Operation with gas Switch to other display areas, e.g.
  • Page 11: Control Unit Operation

    Control unit operation Information in the "Energy cockpit" (cont.) Note When you call up the "Energy cockpit" for the first time, you will be notified that the values shown cannot be used for settling bills with the power supply utility. ■...
  • Page 12 Control unit operation Information in the "Energy cockpit" (cont.) "Energy statement" in conjunction with solar thermal system You can call up the energy status for the last 7 days, for the "Energy cockpit" including the current day. The amount of heat gener- ated from solar power and the energy consumption of in the navigation area the boiler (gas or oil) are shown in kilowatt hours...
  • Page 13 Control unit operation Information in the "Energy cockpit" (cont.) Energy consumption correction factor You can enter a correction factor to adjust the dis- in conjunction with a gas boiler played (calculated) values for energy consumption/fuel consumption to the actual values (as measured by the in conjunction with an oil boiler meter in your home).
  • Page 14 ■ "External program" The operating program set at the control unit has been changed over by another control device. E.g., by your mobile phone with your Viessmann app. You can change the operating program on the Vitotronic control unit. Note The special operating programs are shown on the dis- play in alternation with the boiler water temperature.
  • Page 15: Stopping Central Heating

    Central heating Settings for the room temperature Setting the room temperature Set the required room temperature at the room tem- Room temperature controller operating instruc- perature controller. tions Setting the boiler water temperature (flow temperature) Set a temperature that allows your rooms to become for "Set boiler water temperature"...
  • Page 16: Switching Off Dhw Heating

    DHW heating Setting DHW temperature Set the "Set DHW temperature" for the DHW cylin- "DHW" for DHW heating settings der. Factory setting: 50 °C "DHW set temperature" Tap the following on-screen buttons: for the required value 1. If required, for the home screen to confirm for the "Main menu"...
  • Page 17: Further Adjustments

    Further adjustments Setting the "Language" Tap the following on-screen buttons: "Language" 1. If required, for the home screen 5. Flag for the required "Language" for the "Main menu" to confirm "Settings" Setting the display brightness 2 settings are available to you: "Display brightness"...
  • Page 18: Deactivating The Display Screen For Cleaning

    Enabling the internet interface (LAN) The control unit is equipped with a network module. By to confirm the notification. means of a Viessmann app, you can operate the con- The LAN connection is established automatically trol unit via your smartphone.
  • Page 19 Further adjustments Deactivating the display screen for cleaning (cont.) "Settings" "Clean screen" A timer starts counting. Restoring "Factory settings" Settings and values that are reset: "Settings" Set boiler water temperature ■ ■ Operating program "Factory settings" ■ DHW set temperature to confirm Tap the following on-screen buttons: to cancel the operation.
  • Page 20: Calling Up Help Messages

    Calling up information Calling up help messages You can call up help messages relating to the displays to return to the previous screen. and functions. Tap the following on-screen buttons: to call up the help messages. Calling up information Subject to the components connected and the settings Note made, you can scan current temperatures and operat- Detailed scanning options for the individual groups can...
  • Page 21: Calling Up Service Messages

    Calling up information Calling up service messages Your contractor can set service intervals (limits) (e.g. If you have entered the contact details for your con- for burner hours run). As soon as the limits are excee- tractor (see page 19), these are also displayed. ded, a service message is generated.
  • Page 22: Burner Faults

    In the event of a burner fault, the icon and "Burner fault" are displayed. In conjunction with the Vitotronic 100, type CC1E (see Fig. 3 on page 24) 1. Press the reset button on the boiler burner. You can access the reset button via an opening in the outer panel.
  • Page 23: Emissions Test Mode

    Emissions test mode Emissions test mode Emissions test mode should only be activated by your Note flue gas inspector during the annual inspection. Ensure that enough heat is being drawn during emis- Emissions test mode is enabled for flue gas measure- sions test mode.
  • Page 24: Control Unit Controls

    Switching on and off Control unit controls Vitotronic 100, type CC1E 23.02.17 16:55 °C Fig. 3 Display ON/OFF switch For contractors only: For contractors only: -button to test high limit safety cut-out Temperature limiter For contractors only: Reset button for high limit safety cut-out Vitotronic 100, type CC1I 23.02.17...
  • Page 25: Starting Up The Heating System

    Switching on and off Shutting down the heating system (cont.) 2. Gas boiler: Close the gas shut-off valve. Information on prolonged shutdown Oil boiler: Close the shut-off valves in the oil lines ■ As the circulation pumps no longer run for a longer (at the oil tank and filter).
  • Page 26: Rooms Are Too Cold

    "External program" enabled. The operating program set at the control unit has been changed over by another control device. E.g., by your mobile phone using your Viessmann app. You can change the operating program on the Vitotronic control unit.
  • Page 27: Rooms Are Too Hot

    "External program" enabled. The operating program set at the control unit has been changed over by another control device. E.g., by your mobile phone using your Viessmann app. You can change the operating program on the Vitotronic control unit. There is no hot water...
  • Page 28 "External program" enabled. The operating program set at the control unit has been changed over by another control device. E.g., by your mobile phone using your Viessmann app. You can change the operating program on the Vitotronic control unit. The DHW is too hot...
  • Page 29: Ë And "Service" Are Displayed

    "External program" enabled. The operating program set at the control unit has been changed over by another control device. E.g., by your mobile phone using your Viessmann app. You can change the operating program on the Vitotronic control unit. and "Fault" is displayed...
  • Page 30: "External Hook-Up" Is Displayed

    "External program" is displayed Cause Remedy The operating program set at the control unit has been You can change the operating program. changed over by another control device. E.g., by your mobile phone using your Viessmann app.
  • Page 31: Inspection And Maintenance

    Maintenance Cleaning The control unit can be cleaned with a commercially Note available domestic cleaning agent (non-scouring). You can temporarily deactivate the display screen for You can clean the display screen with a microfibre cleaning: See chapter "Deactivating the display screen cloth.
  • Page 32 If there is damage to the connecting cables or lines of the appliance or externally installed accessories, these must be replaced with special cables or lines. Only use Viessmann cables / lines as replacement. For this, notify your qualified contractor.
  • Page 33: Fuel Oil Additives

    Combustion improvers are additives for optimising fuel Please note oil combustion. Combustion improvers can create residues and Viessmann pressure-jet oil burners do not require impair the safe operation of your heating sys- combustion improvers, as these burners operate with tem.
  • Page 34 Appendix Buttons and icons These symbols are not always displayed, but appear subject to the system version and the operating condi- tion. Buttons and icons in the menu bar Buttons in the menu bar Unknown error on connection Software update is being performed Main menu call-up Establishing a connection "...
  • Page 35: Buttons And Icons

    Appendix Buttons and icons (cont.) Proportion of energy consumption for central heat- Key tone on/off Factory settings restore DHW heating settings menu open LAN internet interface activate/deactivate Temporary deactivation of display screen for clean- Proportion of energy consumption for DHW heat- For the flue gas inspector only: Standard room temperature adjustment Test mode activation...
  • Page 36: Main Menu Overview

    Appendix Menu overview (cont.) "Main menu" overview Note Subject to the features of your heating system, not all of the menu entries shown may be available under Test mode Settings Language Display brightness Brightness, standby Brightness, operation Date and time Date Time Buzzer...
  • Page 37 Appendix Menu overview (cont.) Information General Boiler water temperature Actual boiler output value Sensor 17A Sensor 17B Sensor 9 Flue gas temperature Central fault message Output 20 Output 29 Output 52 Feed pump LON subscriber no. Inputs, extension EA1 Fault message at digital input 1, EA1 extension Fault message at digital input 2, EA1 extension Fault message at digital input 3, EA1 extension External hook-up 0 ..
  • Page 38 Appendix Menu overview (cont.) Information DHW temperature DHW temperature Bottom Heating Operating program Heating and DHW Only DHW Standby mode Screed function External hook-up External program Operating status Solar energy Only in conjunction with solar control module, type SM1: Solar energy bar chart Collector temperature Solar DHW Solar circuit pump...
  • Page 39: Operating Program

    Terminology An app is a software application for a mobile terminal You can operate your heating system using a device, e.g. a mobile phone. Viessmann app. Operating program You define the following with the operating program: Note Central heating and DHW heating An operating program for central heating without DHW ■...
  • Page 40: Heating Circuit

    Appendix Terminology (cont.) Operating status In the "Heating and DHW" operating program, the operating status changes from "Standard heating mode" to "Reduced heating mode" and vice versa. The times at which the operating status is changed over are defined by you when setting the time program. Heating circuit A heating circuit is a sealed unvented circuit that con- A heating system may comprise several heating cir-...
  • Page 41: Information On Disposal

    (Altstoff Recycling Austria AG, licence num- ber 5766). Final decommissioning and disposal of the heating system Viessmann products can be recycled. Components and fluids from your heating systems are not part of ordinary domestic waste. Please contact your heating contractor in connection with the correct disposal of your old system.
  • Page 42 Keyword index Keyword index Fault message Biofuels..............33 – Acknowledging............21 Boiler water temperature..........15 – Scanning..............21 Burner fault..............29 Filter Burner hours run............20 – Drinking water............41 Burner starts...............20 Flow temperature............15 Buttons............... 34 Frost protection............8 Frost protection monitoring........15, 24 Fuel oil additives............
  • Page 43 Keyword index Keyword index (cont.) Operating program Shutting down – Central heating, DHW..........13 – Heating system without frost protection monitoring 24 – DHW only..............40 Signal tone for operation..........17 – Frost protection............14 SM1................20 – Special..............14 Solar circuit pump............10 –...
  • Page 44: Your Contact

    Your contact Contact your local contractor if you have any questions about your system or wish to arrange maintenance or repair work. You can find local contractors on the internet at www.viessmann.de. Viessmann Werke GmbH & Co. KG Viessmann Limited...