Viessmann VITOTRONIC 100 Installation And Service Instructions Manual page 45

Type gc1 digital boiler control unit
Table of Contents

Advertisement

System version 15
Codes must be set on every Vitotronic 100.
Required coding
01 : 2
Multi−boiler system with cascade control via LON BUS
01 : 3
Multi−boiler system with external cascade control via switching
contacts
02 : 2
Modulating burner operation
03 : 1
Only with Vitotronic 100 for low temperature boilers:
Oil fired operation (irreversible)
0d : 0
Only with Vitotronic 100 for Vitocrossal 300:
Without Therm−Control
Automatic changeover
4A: 1
Only with Vitotronic 100 for low temperature boilers:
Connecting temperature sensor T1 to plug aJA
4b : 1
Only with Vitotronic 100 for low temperature boilers:
Connecting temperature sensor T2 to plug aJB
*1
If required.
(cont.)
*1
*1
Heating system designs