Gas piping — sizing gas lines
Natural Gas:
Pipe sizing for natural gas
1.
Size gas piping from meter outlet to entrance of boiler in accordance
with Figure 95 and Figure 96.
2.
Use total input of all boilers. Divide total input in Btuh by 1,000 to
obtain cubic feet per hour of natural gas.
a.
Pipe lengths in
Figure 95 are equivalent length of straight pipe. Con-
vert pipe fittings to equivalent lengths using data from Figure 96.
b. Figure 95 is only for natural gas with specific gravity 0.60, with a
pressure drop through the gas piping of 0.30" w.c.
c.
For additional gas pipe sizing information, refer to ANSI Z223.1
(or B149.1 or B149.2 for Canadian installations).
Natural gas supply pressure
1.
Pressure required at gas valve inlet pressure port:
a.
Maximum: 13" w.c. with no flow (lockup) or with boiler on
b.
Minimum: 4" w.c. (for all except 5" for -299) with gas flowing
(verify during boiler startup, while boiler is at high fire)
2.
Install 100% lockup gas pressure regulator in supply line if inlet pres-
sure can exceed 13" w.c. at any time. Adjust lockup regulator for 13"
w.c. maximum.
Propane Gas:
You must follow the instructions, beginning on page 7, to
operate the boiler on propane. Failure to comply could result
in severe personal injury, death or substantial property dam-
age.
Pipe sizing for propane gas
1.
Contact gas supplier to size pipes, tanks and 100% lockup gas pressure
regulator.
Propane supply pressure
1.
Adjust propane supply regulator provided by gas supplier for 13" w.c.
maximum pressure.
2.
Pressure required at gas valve inlet pressure port:
a.
Maximum: 13" w.c. with no flow (lockup) or with boiler on
Minimum: 4" w.c. with gas flowing (verify during boiler startup,
while boiler is at high fire).
Manifolded gas supply lines
1.
Construct gas header for multiple boilers using
sizing tables below. Refer to the National Fuel Gas Code for other
conditions.
2.
Provide manual shutoff gas valve and ground joint union as shown in
Figure 31 and Figure 94 for each boiler. When gas line enters from top
of the boiler, the boiler internal gas piping provides a drip leg.
3.
A ¾" NPT gas piping riser from header to boiler will be large enough
for most jobs. Ensure the piping is large enough so that the minimum
pressure at the boiler will be at least 5 inches water column with all
connected appliances firing.
Part number 550-100-090/0809
— Boiler Manual
Figure 94
Figure 95
total length,
Figure 96
Figure 94 and the
Common gas line for multiple boilers
Pipe capacity for 0 60 specific gravity
natural gas
Capacity
Gas pipe
(cubic feet per hour, 0 60 specific gravity)
feet
1"
1¼"
10
520
1050
20
350
730
30
285
590
40
245
500
50
215
440
75
175
360
100
150
305
150
120
250
Equivalent lengths of straight pipe for
typical gas line fittings
Equivalent length, feet
Pipe size
inches
90° Elbow
1
2 62
3 45
4 02
2
5 17
6 16
1½"
2"
2½"
1600
3050
4800
1100
2100
3300
890
1650
2700
760
1450
2300
670
1270
2000
545
1020
1650
460
870
1400
380
710
1130
Tee
5 24
6 90
8 04
10 3
12 3
77