Page 2
Boiler loop circulator (by installer) — Recommended sizing is for a 30°F temperature rise (= 35 GPM for Ultra-550 or 45 GPM for Ultra-750) — Allow 11 feet w. c. head loss through boiler at recommended flow rates (Taco 1400-50 or equivalent) Gas, 1¼”...
Page 3
Couplings (include termination, used for vertical vent or sidewall vent if no external upwards extension) Return bend, 180-degree (vertical air-pipe termina- tion) Reducers, 8"x6" (for Ultra-750 only when using (direct exhaust) 8-inch vent and/or air piping) (direct vent) Louvers for ventilation openings, when specified in boiler manual SNORKELING OPTION —...