Weil-McLain Ultra 3 series User Manual page 59

Gas-fired water boilers ultra 3 series;
Hide thumbs Also See for Ultra 3 series:
Table of Contents

Advertisement

-
gas
fired water boiler
Multiple boiler water piping
Figure 64
Piping layout — typical piping for multiple Ultra boilers, with DHW storage heaters (4-boiler system)
1
Flow/check valve (each boiler)
2
Isolation valves (when used)
3
Caps
4
Easy-Fit® Manifold (supply) — layout
and size per page 56
5
Easy-Fit® Manifold (return) — layout
and size per page 56
6
Primary circulator
7
Expansion tank (diaphragm type)
8
System air eliminator
9
System automatic air vent
13
Cold water supply
17
Boiler circulator (each boiler)
18
System supply
19
System return
20
Boiler relief valve and discharge piping,
installed per Ultra Boiler Manual
Part number 550-100-090/0809
— Boiler Manual
Legend — Figure 64
21
Indirect-fired storage water heaters (Weil-McLain PLUS Line shown) — Example is
shown with reverse-return boiler-side piping using a single circulator. Alternate: each
water heater could have its own circulator.
22
Boiler water inlet
23
Boiler water outlet
24
DHW boiler-side circulators
25
DHW boiler-side supply Easy-Fit® Manifold
26
DHW boiler-side return Easy-Fit® Manifold
27
Flow/check valves (to prevent induced or gravity flow in heating system or DHW
piping)
28
Check valve to prevent heat migration in heating system
29
See water heater manual for DHW piping — The DHW piping must also be mani-
folded together since the boiler-side piping is manifolded. If DHW heaters supply
separate DHW circuits, provide an individual circulator for each water heater, and
control each circulator by its water heater's aquastat.
Strap system supply and return sensors to lines as shown, at least 6 pipe
30
diameters (but no more than 3 feet) from boiler connection tees.
(continued)
Flow rate
Suggested DHW
1 – 3.9 gpm
boiler-side pipe
sizing
(for max 0.04
3.9 – 7.1 gpm
feet head loss per foot of
7.1 – 16 gpm
total equivalent length,
TEL)
16 – 24 gpm
Size
Flow rate
Size
¾"
24 – 45 gpm
2"
1"
45 – 75 gpm
2½"
1¼"
75 - 140 gpm
3"
1½"
140 – 290 gpm
4"
This piping is sug-
gested only. The
layout above should be controlled
with a boiler sequencing panel that
provides DHW operation as well.
Wire the heating system circulator
to operate only on call for heat. Al-
ternatively, use the boiler sequencing
panel to provide domestic priority
by disabling the heating system cir-
culator any time there is a DHW call
for heat. The boiler circulators, item
17, must operate on any call for heat,
whether heating system or DHW.
Offset the DHW boiler-side supply
and return manifolds as shown so
the total run of pipe and fittings to
each of the water heaters is approxi-
mately equal.
59