Toshiba RAS-15EKV-UL Service Manual page 24

Indoor and outdoor unit air conditioner split tye
Hide thumbs Also See for RAS-15EKV-UL:
Table of Contents

Advertisement

7-2. Op eration Data
<Cooling>
Tempeature
Model name
condition [°F (°C)]
Indoor
Outdoor
80/67
98/75
(26.7/19.4) (35/23.9)
<Heating>
Tempeature
Model name
condition [°F (°C)]
Indoor
Outdoor
70/60
47/43
(21.1/15.6)
(8.3/6.1)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 25 ft (7.5m)
Standard
RAS-
pressure
P [psi (MPa)] T1 [°F (°C)]
131 to 160
15EKV-UL
(0.9 to 1.1)
131 to 160
17EKV-UL
(0.9 to 1.1)
131 to 160
22EKV-UL
(0.9 to 1.1)
Standard
RAS-
pressure
P [psi (MPa)] T1 [°F (°C)]
363 to 392
15EKV-UL
(2.5 to 2.7)
377 to 406
17EKV-UL
(2.6 to 2.8)
116 to 145
22EKV-UL
(0.8 to 1.0)
Heat exchanger
T2 [°F (°C)]
52 to 55
40 to 42
(11 to 13)
(37 to 39)
52 to 55
40 to 42
(11 to 13)
(42 to 44)
52 to 55
41 to 43
(11 to 13)
(42 to 44)
Heat exchanger
pipe temp.
T2 [°F (°C)]
102 to 105
32 to 37
(39 to 41)
(0 to 3)
106 to 106
32 to 36
(41 to 43)
(0 to 2)
52 to 55
104 to 107
(11 to 13)
(42 to 44)
- 24 -
FILE NO. SVM-13070
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
High
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
High
High
Compressor
revolution
(rps)
57
62
88
Compressor
revolution
(rps)
74
82
84