Altitude Derate Multiplier For U.s.a - Carrier 59SC2C Series Installation, Start-Up, Operating And Service And Maintenance Instructions

Single stage 4-way multipoise condensing gas furnace series 1
Table of Contents

Advertisement

Table 19 – Altitude Derate Multiplier for U.S.A.
ALTITUDE
FT.
M
0–2000
0--- 610
2001–3000
610--- 914
3001–4000
914--- 1219
4001–5000
1219--- 1524
5001–6000
1524--- 1829
6001–7000
1829--- 2134
7001–8000
2134--- 2438
8001–9000
2438--- 2743
9001–10,000
2743--- 3048
*Derate multiplier factors are based on midpoint altitude for altitude range.
SINGLE-STAGE
ON/OFF Switch
1/2" NPT Inlet
1/8" NPT Inlet
Pressure Tap
Fig. 58 - - Gas Valve
PERCENT
DERATE
OF
MULTIPLIER
DERATE
FACTOR*
0
1.00
4--- 6
0.95
6--- 8
0.93
8--- 10
0.91
10--- 12
0.89
12--- 14
0.87
14--- 16
0.85
16--- 18
0.83
18--- 20
0.81
Regulator Seal Cap
Regulator Adjustment
Regulator Seal Cap under Cap
1/2" NPT Outlet
1/8" NPT Manifold
Pressure Tap
A11153
Fig. 59 - - Orifice Hole
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
5.0 AMPS ON AMMETER
EXAMPLE:
10 TURNS AROUND JAWS
Fig. 60 - - Amp. Draw Check with Ammeter
68
BURNER
ORIFICE
A93059
HOOK-AROUND
AMMETER
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
A96316