EDIT DETECTOR
1=ZONE ASSIGNMENT
00 ** ** ** **
Edit Detector Screen #4
See Page
EDIT DETECTOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Detector Screen #5
MS-9050UD Series PN 52413:D 12/15/08
With the preceding program settings, when the detector with address 005 is activated, zone Z18
will cause its associated control module to activate immediately, sounding the connected
signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone
Z001 will cause its associated control module to activate and the control panel will initiate an
alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Zone Assignment
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while
viewing Edit Detector Screen #4 displays the following screen:
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default
for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on
the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this device. The cursor moves to the next Z** designation. Continue entering zone
assignments or the remaining zones can be left blank or programmed as general alarm zone
Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Detector Screen #4. Note that the left and right
arrow keys can be used to navigate through the zones and the CLEAR key can be used to
quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will
cause the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Zone Assignment Screen
Noun/Adjective Screen
Programming
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udMs-9050ude

Table of Contents