General - Group 1 - Viessmann VITODENS 222-F Installation And Service Instructions Manual

Compact gas condensing boiler 4.8 to 35 kw natural gas and lpg version gc no 47-819-15 (19kw); 47-819-16 (26kw); 47-819-17 (35kw)
Table of Contents

Advertisement

General – Group 1
Coding
Coding in the delivered condition
11:≠9
No access to the coding
addresses for the param-
eters of the combustion
controller
25:0
Without outside tempera-
ture sensor
52:0
Without flow temperature
sensor for low loss
header
53:3
Never adjust
54:0
Never adjust
6E:50
Never adjust
76:0
Without LON communi-
cation module (only for
weather-compensated
control)
79:1
With LON communication
module: Control unit is
fault manager (only for
weather-compensated
control)
7b:1
With LON communication
module: The control unit
transmits the time (only
for weather-compensa-
ted control)
80:1
A fault message is dis-
played, providing a fault
is active for at least 5 s
Possible change
11:9
Access open to the coding
addresses for the parame-
ters of the combustion con-
troller
25:1
With outside temperature
sensor and fault monitoring
of the sensor (automatic
recognition)
52:1
With flow temperature sen-
sor for low loss header
(automatic recognition)
76:1
With LON communication
module (automatic recog-
nition)
79:0
Control unit is not fault
manager
7b:0
Do not transmit time
80:0
Immediate fault message
80:2
The minimum fault duration
to
before a fault message is
80:199
issued is adjustable from
10 s to 995 s; 1 step ≙ 5 s
Code 2
75