Scanning And Resetting The "Service" Display - Viessmann VITODENS 222-F Installation And Service Instructions Manual

Compact gas condensing boiler 4.8 to 35 kw natural gas and lpg version gc no 47-819-15 (19kw); 47-819-16 (26kw); 47-819-17 (35kw)
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
4. Select subscriber (e.g. subscriber
10).
The subscriber check for the selected
subscriber is introduced.
■ Successfully tested subscribers
are designated with "OK".
■ Unsuccessfully tested subscribers
are designated with "Not OK".
Note
To carry out a new subscriber check,
create a new subscriber list with
menu item "Delete list?"

Scanning and resetting the "Service" display

After the limit values specified in coding address "21" and "23" have been reached,
the following appears on the programming unit display:
■ On a constant temperature control unit:
The specified hours run or the specified interval with clock symbol "u" (subject to
setting) and " "
■ On a weather-compensated control unit:
"Service" and " "
Scanning and resetting service
Press OK to acknowledge a service
message.
Note
An acknowledged service message that
was not reset reappears:
■ On a weather-compensated control
unit, on the following Monday.
■ On a constant temperature control
unit, after seven days.
58
(cont.)
Note
If the subscriber check is carried out
by another control unit, the sub-
scriber number and "Wink" are
shown on the display for approx.
1 min.
After a service has been carried out
(reset service)
Weather-compensated control unit
1. Press OK and
simultaneously for
approx. 4 s.
2. "Service functions"
3. "Service reset"
Note
The selected service parameters for
hours run and time interval restart
at 0.