Calling Up Code 1 - Viessmann VITODENS 222-F Installation And Service Instructions Manual

Compact gas condensing boiler 4.8 to 35 kw natural gas and lpg version gc no 47-819-15 (19kw); 47-819-16 (26kw); 47-819-17 (35kw)
Table of Contents

Advertisement

Code 1

Calling up code 1

Note
■ On weather-compensated control
units, codes are displayed as plain
text.
■ Codes that have no function due to the
heating system equipment level or the
setting of other codes are not dis-
played.
■ Heating systems with one heating cir-
cuit without mixer and one heating cir-
cuit with mixer:
The heating circuit without mixer is
designated with "Heating circuit 1"
and the heating circuit with mixer with
"Heating circuit 2".
If the heating circuits were given indi-
vidual designations (see page 28), the
selected designation and "HC1" or
"HC2" appears instead of the above.
Weather-compensated control unit:
1. Press OK and
simultaneously for
approx. 4 s.
2. "Coding level 1"
3. Select group of required coding
address (see following section):
For example "General".
4. Select coding address.
5. Select value according to the follow-
ing tables and confirm with OK.
62
6. If you want to reset all codes to the
delivered condition:
Select "Standard setting" in "Cod-
ing level 1".
Constant temperature control unit:
1. Press OK and
simultaneously for
approx. 4 s.
2. With , select "1" for coding level 1
and confirm with OK.
"I" flashes on the display for the cod-
ing addresses in group 1.
3. Select group of the required coding
address with / . For example, "1" for
group "General" (see following sec-
tion):
Confirm selected group with OK.
4. Select coding address with / .
5. Select value according to the follow-
ing tables with / and confirm with
OK.
6. If you want to reset all codes to the
delivered condition:
Select
"6" and confirm with OK.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 222-f fs2a

Table of Contents