12-1-3. Cabling and Setting of Remote Controller Control
RAV-SM560UT-E, RAV-SM560BT-E,
RAV-SM800UT-E, RAV-SM800BT-E (A02-014)
2-remote controller control (Controlled by two remote controllers)
One or multiple indoor units are controlled by two remote controllers.
(Max. 2 remote controllers are connectable.)
• 1 indoor unit is controlled by 2
remote controllers
(Setup method)
One or multiple indoor units are controlled by two
remote controllers.
(Max. 2 remote controllers are connectable.)
<Wired remote controller>
How to set wired remote controller to sub remote
controller
Insert the remote controller address connector
provided on the rear side of the remote controller
switch P .C. board into Sub in exchange for Master.
<Wireless remote controller>
How to set wireless remote controller to sub
remote controller
Change OFF of Bit [3: Remote controller Sub/
Master] of switch S003 to ON.
[Operation]
1. The operation contents can be changed by Last-push-priority.
2. Use a timer on either Master remote controller or Sub remote controller.
Remote controller
switch (Master)
Rear side of remote
controller P.C. board
Sensor
cover
Adjust
corner cap
– 154 –
www.ilmalämpöpumput.com
RAV-SM560/800UT-E
RAV-SM560/800BT-E
Remote controller
switch (Sub)
Sold separately
Sold separately
Remote controller
cables (Procured locally)
Terminal block for
remote controller cables
A
B
Indoor unit
1
2
3
1
2
3
nit
Outdoor u
Remote controller
address connector
S003
Master remote
controller
Sub
remote controller
Bit 1 : OFF to ON
ON
Sensor P.C. board