Lock Time and Fail-Safe / Fail-Secure Settings
Each of the two lock relays can be set to operate the lock for between 1 and 49 seconds.
Each relay may also be set to open or close when operated, allowing the use of Fail-Safe
(power to lock) or Fail-Secure (power to release) locks.
Lock 1 may also be set to operate in a Toggle function — see Set-Reset Latch for details.
Adjusting Lock Time and Fail-Safe / Fail-Secure Settings
1. Present an Editor Key:
2. Choose a door:
Press to change
Door 1 settings:
3. Change the lock time?
Press to
change
tens:
4. Change the Fail-Safe / Fail-Secure Setting?
Press the middle button :
Press to change
Door 2 settings:
Press to
change
units:
32
Editor Key : 0
1:Y 2:Y
Lock1 Time : 3
Fail‐Safe
Lock1 Time : 10
Fail‐Safe
Lock1 Time : 10
Fail‐Secure