Unit Control Board Flash Codes - York Sunline Magnum DJ180 Installation Manual

Sunline magnum gas/electric single package air conditioners
Hide thumbs Also See for Sunline Magnum DJ180:
Table of Contents

Advertisement

each alarm flash code by approximately 2 seconds. In
all cases, a flashing Green LED will be used to indicate
non-alarm condition.
In some cases, it may be necessary to "zero" the
ASCD for the compressors in order to perform trouble-
TABLE 27: UNIT CONTROL BOARD FLASH CODES
FLASH CODE
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Control waiting ASCD
3 Flashes
HPS1 Compressor Lockout
4 Flashes
HPS2 Compressor Lockout
5 Flashes
LPS1 Compressor Lockout
6 Flashes
LPS2 Compressor Lockout
7 Flashes
FS1 Compressor Lockout
8 Flashes
FS2 Compressor Lockout
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
Compressors locked out because the Economizer is using free
11 Flashes
Cooling
1
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
13 Flashes
Compressor Held Off due to Low Voltage
14 Flashes
EEPROM Storage Failure
OFF
No Power or Control Failure
1.
Non-alarm condition.
64
DESCRIPTION
1
1
shooting. To reset all ASCDs for one cycle, press and
release the UCB TEST/ RESET button once.
Flash codes that do and do not represent alarms are
listed in Table 27.
GREEN
RED
LED
LED
16
-
-
Flashing
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
Flashing
On
1
Flashing
On
Off
On
Flashing
On
Off
On
Off
Off
284809-YIM-B-0707
RED
RED
LED
LED
8
4
2
-
-
-
-
-
-
Off
On
Off
On
On
Off
On
Off
On
On
On
On
Off
Off
Off
Off
Off
On
Off
On
On
Off
On
Off
On
On
Off
Off
Unitary Products Group
RED
LED
1
-
-
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Off

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents