Operation Mode - Theben PresenceLight 180A-KNX series Operating Manual

Presence detector
Table of Contents

Advertisement

Activation
Powerup

5.5 Operation mode

The PresenceLight 180x-KNX and PresenceLightx-360 KNX have 3 operation modes:
● Normal
● Test presence (page 75)
5.6 Switch-on behaviour
After every time the bus voltage is switched or the parameters are downloaded by
ETS, the detector runs through its start-up phase (indicated by LED).
1. Start-up phase (30 seconds)
● LED blinks once per second
● Switching: outlet light receives an ON telegram irrespective of brightness
● Constant light control: control is inactive, lighting is maximum dimmed (Value
telegram 100 %).
● If there is no presence or sufficient brightness, an OFF telegram is sent after
30 sec. (Light off).
2. Operation mode normal
● The detector is ready for use (LED off)
3. Event of malfunction
● LED flashes rapidly
● Troubleshooting see page 80
72
Description
Press and hold the program button while switching on the bus voltage.
● Test light (page 77)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents