Rigid Venting Systems Installation Instructions
Component Installation Guide
Single-pipe vent starter adaptor installation
Fig. 84 Installing single-pipe vent adaptor for
stainless steel and CPVC (not required for PP(s)
vent system)
Vitodens 100-W WB1B 26, 35 and 200-W WB2B
19, 26, 35
Fig. 85 Vitodens 200-W WB2B 45, 60, 80, 105.
Installing single-pipe vent adaptor for stainless
steel and CPVC vent systems [not required for
PP(s)]
For PP(s) vent system, see page 75.
Single Pipe Venting (Room Air Dependent)
(continued)
WARNING
Prior to installation, ensure the specially designed single-
pipe vent adaptor end is smooth and chamfered to
prevent possible
damage to the sealing gasket of the boiler vent pipe
adaptor (coaxial).
Failure to comply could result in leakage, potentially
causing personal injury or death.
1. Apply small amount of water to end of single-pipe vent
adaptor to ease insertion.
2. Slide special single-pipe vent adaptor 1 fully onto
boiler vent pipe adaptor 2 . Do not apply excessive
force and/or bend single-pipe vent adaptor 1 when
inserting. Force could damage gasket.
IMPORTANT
The boiler vent pipe adaptor comes pre-installed for all
Vitodens 100-W and 200-W boilers.
Ceiling/Roof opening
Cut an opening for the vent pipe.
Size opening at least 1 in. (25 mm) larger than vent pipe
diameter (for combustible as well as non-combustible
material).
81