5.7

Polling event memory

Siemens Building Technologies
Fire & Security Products
Overview
This function is only available with control units with an indicator module.
The event memory records event with date and time. These event can be polled at
any time. Each event has an event number. This number is displayed on the indi-
cator module (e.g. E.012.). The most recent event has the lowest number (E.001.).
The event is indicated by means of the LED. An alarm on zone 4, for example, is
indicated by the red zone LED 4.
Procedure
To poll the event memory, proceed as follows:
1. Enable the operating level 2 (password or key).
2. Keep the key 'Acknowledge' pressed and enter the code '1122' with the numeri-
cal keys.
The indicator module displays 'E.001.' (most recent event).
The type of event is indicated by the LEDs (see table below).
3. Poll the year of the event with the numeric key '1', the month with the key '2' and
the time with the key '3'.
The indicator module displays e.g. '2004'
4. To indicate the next event, press the key 'Reset'.
The indicator module displays 'E.002'.
To get back to the most recent event, press the numeric key '4'.
The indicator module displays 'E.001.'
5. To quit the event memory, press the numeric key 'Acknowledge'.
The system is in normal operating condition again.
You will quit the event memory automatically when you do not enter any data for
more than one minute.
Indication
Red zone LED
'Remote transmission'
'Part of system OFF'
'Fault'
'Evacuation'
Meaning of the LED display
Tab. 4
Signification
Alarm of the corresponding zone
Remote transmission activated
System part has been out of service
A fault has occurred in the system
Evacuation has been activated
Operation
25
007995_a_en_--.doc
04.2004