Messages List - GE Digital Energy SitePro 400 VAC CESeries 7 Operating Manual

Uninterruptible power supply
Table of Contents

Advertisement

7.7.2 Messages list

Code
Message
WATCHDOG
4002
RESET
RECTIFIER
4111
MAINS OK
BATTERY TEST
4119
STARTED
BATTERY TEST
4120
STOPPED
RECTIFIER
4161
ON
RECTIFIER
4162
OFF
GENERATOR
4163
ON
GENERATOR
4164
OFF
INVERTER
4302
CANNOT BE
TURNED ON
INVERTER
4303
CANNOT BE
TURNEDOFF
INVERTER
4361
ON
INVERTER
4362
OFF
BYPASS MAINS
4411
OK
COMMAND
4500
LOAD OFF
NO BYPASS
4521
POWER
MULTIPLE LOAD
4534
TRANSFER
BYPASS
4535
LOCKED
BYPASS
4536
FREE
Modifications reserved
OPM_SPE_XXX_60K_60K_7GB_V010.doc
The microprocessor has detected an incorrect operation:
transfers the load on mains and performs a program reset.
The inverter will restart automatically and will supply the load.
Rectifier input mains is again within the admitted tolerance
(voltage, frequency and phase).
Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined by
parameters.
End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.
Rectifier received the command to switch ON.
Rectifier received the command to switch OFF for:
input mains out of tolerance / EPO / UDC max.
Customer interface (X1 - 11, 22) received a Gen-set ON signal.
Operating mode depend on setting of parameters.
Customer interface (X1 - 11, 22) received a Gen-set OFF signal.
Function Bypass enabled depends on setting of respective
parameter.
Inverter cannot be switched on because one of the following
conditions is still present:
Overtemperature.
-
Low battery voltage.
-
Inverter fuses.
-
Overload.
-
K7 opening failure.
-
High battery voltage.
-
DC low.
-
EPO.
-
Inverter cannot be switched OFF, because the load cannot be
switched to mains (voltage out of tolerance, not synchrony, BP
blocked).
The command to start the inverter has been activated on the
control panel.
The command to switch OFF the inverter has been activated by
the control panel or automatically for alarm presence.
Bypass input mains is again within tolerance (voltage,
frequency and phase).
Disconnection of the load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop operation
With the load supplied by electronic bypass, a mains failure or
K6 opening occurred.
2 transfers inverter- mains has been detected in a short time,
defined by parameter (default 30 sec.).
Bypass to mains not enabled due to settings of parameters.
Contactor K6 is open.
Settings of parameters enable Bypass transfer on mains.
Contactor K6 can be closed.
Meaning
Operatine Manual SitePro 60 kVA
Pagina 60/90