Ceiling Type
Relocation
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous
for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage,
noise and / or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or
other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly
resulting in rupture, injury or other trouble.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY
OZONE LAYER.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is
approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also
been changed. Therefore, do not let water, dust, former refrigerant, or refrigerating oil enter the refrigerating cycle
during installation work.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of
the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not
enter.
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at
least 3 mm.
The installation fuse (all types can be used) must be used for the power supply line of this conditioner.
(*1) Refer to the "Definition of Qualified Installer or Qualified Service Person."
7-EN
Installation Manual
Ceiling Type
2

Accessory Parts

Part name
Installation Manual
Owner's Manual
CD-ROM
Heat insulating pipe
Installation pattern
Washer
Hose band
Drain hose
Bushing
Heat insulator
Heat insulator of top plate
Banding band
– 4 –
Q'ty
Shape
(Hand over to customers)
1
This manual
(For other languages that do not appear in this Installation Manual,
please refer to the enclosed CD-R.)
(Hand over to customers)
1
(For other languages that do not appear in this Installation Manual,
please refer to the enclosed CD-R.)
1
Owner's Manual and Installation Manual
2
For heat insulation of pipe connecting section
1
Drawing-out port of hanging bolt pipe
4
M10 × Ø25
For holding down unit
2
For connecting drain pipe
1
For connecting drain pipe
1
For protection of edge at power taking-in port
1
For heat insulation of drain hose (10 t × 190 × 190)
1
For upper pipe hole of indoor unit (6 t × 130 × 160)
2
For prevention of open of drain hose heat insulator
Installation Manual
Usage
EN
8-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm804ct-eRav-sm1104ct-eRav-sm1404ct-e

Table of Contents